Wire The Module - AB Quality 1756-ENBT ControlLogix Installation Instructions Manual

Ethernet/ip bridge module
Table of Contents

Advertisement

12 ControlLogix™ Voltage/Current Input Module

Wire the Module

You can only connect wiring to your module through an RTB or IFM.
The example below shows how to wire the module.
Channel 0
Shield
ground
Channel 3
2-Wire
Transmitter
1. Use the following chart when wiring your module in differential mode
NOTES:
This channel:
Channel 0
Channel 1
Channel 2
Channel 3
2. When operating in 4 channel, high speed mode, only use channels 0, 2, 4 and 6.
3. All terminals marked RTN are connected internally.
4. A 249 W current loop resistor is located between IN-x and i RTN-x terminals.
5. If multiple (+) or multiple (-) terminals are tied together, connect that tie point to a
terminal to maintain the module's accuracy.
Publication
1756-IN039D-EN-P - February 2003
1756-IF16 Differential current wiring example
i
IN-0
A
IN-1
IN-2
IN-3
RTN
IN-4
i
IN-5
IN-6
A
IN-7
IN-8
IN-9
IN-10
IN-11
RTN
IN-12
IN-13
IN-14
IN-15
Uses these terminals:
IN-0 (+), IN-1 (-) & i RTN-0
IN-2 (+), IN-3 (-) & i RTN-2
IN-4 (+), IN-5 (-) & i RTN-4
IN-6 (+), IN-7 (-) & i RTN-6
i RTN-0
2
1
i RTN-1
4
3
i RTN-2
6
5
8
7
i RTN-3
10
9
RTN
12
11
i RTN-4
14
13
i RTN-5
16
15
i RTN-6
18
17
i RTN-7
20
19
i RTN-8
i RTN-9
22
21
i RTN-10
24
23
26
25
i RTN-11
RTN
28
27
30
29
i RTN-12
32
31
i RTN-13
i RTN-14
34
33
36
35
i RTN-15
This channel:
Uses these terminals:
Channel 4
IN-8 (+), IN-9 (-) & i RTN-8
Channel 5
IN-10 (+), IN-11 (-) & i RTN-10
Channel 6
IN-12 (+), IN-13 (-) & i RTN-12
Channel 7
IN-14 (+), IN-15 (-) & i RTN-14
Jumper
wires
40912-M