Where To Find Information On Configuring The Module - AB Quality 1756-ENBT ControlLogix Installation Instructions Manual

Ethernet/ip bridge module
Table of Contents

Advertisement

Link Status Indicator
The Link Status LED provides the following information:
State
Off
Green
Flashing Green
OK Status Indicator
The OK Status LED provides the following module information:
State
Off
Flashing Green
Green
Flashing Red
Red
Flashing Red and Green Self Test

Where to Find Information on Configuring the Module

To configure your module, refer to the configuration chapter of your
EtherNet/IP Modules User Manual, publication number ENET-UM001,
available online at www.rockwellautomation.com/literature.
ControlLogix EtherNet/IP Bridge Module 17
Status
No data transmission
Ready
Data transmission in
progress
Status
No Power
Standby
Operational
Minor Fault
Major Fault
Publication
Description
Module is not ready to communicate.
Module is ready to communicate.
Module is communicating over the
network.
Description
Module does not have 24V DC power.
Verify there is chassis power and the
module is completely inserted into
chassis and backplane.
Module is not configured.
Module is operating correctly.
A recoverable fault has been detected.
This could be caused by an error in the
configuration.
An unrecoverable fault has been
detected. Recycle power to the module.
If this does not clear the fault, replace
the module.
Module performing power-up self-test.
1756-IN019C-EN-P - November 2004