Connect A Battery - AB Quality 1756-ENBT ControlLogix Installation Instructions Manual

Ethernet/ip bridge module
Table of Contents

Advertisement

22 ControlLogix® Controller and Memory Board

Connect a Battery

When you connect or disconnect the battery an electrical
WARNING
arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is
removed or the area is nonhazardous before proceeding.
For Safety information on the handling of lithium
batteries, including handling and disposal of leaking
batteries, see Guidelines for Handling Lithium Batteries,
publication AG 5-4.
To prevent possible battery leakage, even if the BAT LED
ATTENTION
is off, replace a 1756-BA1 or 1756-BA2 battery according
to the following schedule:
If the temperature 1 in.
below the chassis is:
0° ... 35° C
36° ... 40° C
41° ... 45° C
46° ... 50° C
51° ... 55° C
56° ... 60° C
Store batteries in a cool, dry environment. We
ATTENTION
recommend 25°C with 40%...60% relative humidity. You
may store batteries for up to 30 days between
-45°...85°C, such as during transportation. To avoid
leakage or other hazards, do not store batteries above
60°C for more than 30 days.
Publication
1756-IN101J-EN-P - November 2004
Replace the battery within:
No required replacement
3 years
2 years
16 months
11 months
8 months