Specifications - 1784-Cf64 Industrial Compactflash Card - AB Quality 1756-ENBT ControlLogix Installation Instructions Manual

Ethernet/ip bridge module
Table of Contents

Advertisement

44 ControlLogix® Controller and Memory Board

Specifications - 1784-CF64 Industrial CompactFlash Card

Description
User Available Memory
Nonvolatile Memory
Weight
Operating Temperature
Storage Temperature
Relative Humidity
Vibration
Operating Shock
Non-Operating Shock
Emissions
ESD Immunity
Radiated RF Immunity
Publication
1756-IN101J-EN-P - November 2004
Value
64M bytes
Yes
14.2 g (0.5 oz).
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
• 0 ... 60°C (32 ... 140°F)
IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
• -40 ... 85°C (-40 ... 185°F)
IEC 60068-2-30 (Test Db, Un-packaged Non-operating
Damp Heat):
• 5% ... 95% noncondensing
IEC60068-2-6 (Test Fc, Operating):
• 2g @ 10-500Hz
IEC60068-2-27 (Test Ea, Unpackaged Shock):
• 30g
IEC60068-2-27 (Test Ea, Unpackaged Shock):
• 50g
CISPR 11:
• Group 1, Class A
IEC 61000-4-2:
• 4kV contact discharges
• 8kV air discharges
IEC 61000-4-3:
• 10V/m with 1kHz sine-wave 80%AM from 30MHz...2000MHz
• 10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
• 10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz