Fujitsu primequest 2400E2 Design Manual page 61

2000 series
Table of Contents

Advertisement

2.10 Peripheral Configuration (4/4)
Rack Installation Requirements
A. Allowable spacing between posts: 685 to 790mm
B. Distance from the inside of the front door to the outside
of the front rack posts: 60mm or more
C. Distance from the outside of the front rack posts to the inside
of the rear door: 860mm or more
For details on rack installation conditions, refer to "Hardware Installation Manual".
PRIMEQUEST 2000 Series Design Guide
Front door
Front
Posts
B
A
C
60
Rear door
Posts
Copyright 2016-2017 FUJITSU LIMITED

Advertisement

Table of Contents
loading

Table of Contents