Particulate and gaseous contamination specifications

The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous contamination. If
the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility of the customer.
NOTE:
This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous
contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified in the following
table and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the
environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the
responsibility of the customer.
Table 18. Particulate contamination specifications
Particulate contamination
Air Filtration
NOTE:
Applies to data center environments only. Air filtration
requirements do not apply to IT equipment designed to be used
outside a data center, in environments such as an office or
factory floor.
Conductive Dust
NOTE:
Applies to data center and non-data center
environments.
Corrosive Dust
NOTE:
Applies to data center and non-data center
environments.
Table 19. Gaseous contamination specifications
Gaseous contamination
Copper Coupon Corrosion Rate
Temperature or Specification
Six consecutively executed shock pulses in the positive and
negative x, y, and z axes (one pulse on each side of the
system) of 105 G for up to 2 ms.
3,048 m (10,000 ft)
35,000 m (10,688 ft)
Maximum temperature is reduced by 1 °C/300 m (1 °F/547
ft) above 950 m (3,117 ft).
Maximum temperature is reduced by 1 °C/175 m (1 °F/319
ft) above 950 m (3,117 ft).
Maximum temperature is reduced by 1 °C/125 m (1 °F/228
ft) above 950 m (3,117 ft).
Specifications
Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
NOTE:
MERV11 or MERV13 filtration.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
Specifications
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
Air entering the data center must have
Technical specifications
21