Siemens SIMATIC S7-300 Hardware And Installation Manual page 53

Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Rule: Ground the cable shielding
You should always connect both ends of the cable shielding to ground/functional
ground, since this is the only way to achieve good interference suppression in the
higher frequency range.
If you connect only one end of the shielding (that is, at one or the other end of the
cable) to ground, you will merely achieve an attenuation in the lower frequency
range. One-sided shielding connections could be more favorable in situations
• not allowing the installation of an equipotential bonding conductor,
• LI DQDORJ VLJQDOV VRPH P$ RU $ DUH WUDQVPLWWHG
• or if foil shielding is used (static shielding).
Note
Potential differences between two grounding points might cause an equipotential
current flow across shielding connected at both ends. In this case you should
install an additional equipotential bonding conductor..
Caution
Always avoid the flow of operating current to ground.
Details on cable shielding and equipotential bonding ...
are found in the Appendix under the same topic.
Rule: Ground the load circuits
You should always ground the load circuits. This common reference potential
(earth) ensures proper functioning.
Tip:
If you want to locate a short to ground, provide your load power supply (Terminal
L– or M) or the isolating transformer with a removable connection to the protective
conductor (see Overview: Grounding Number 4).
This tip does not apply to CPUs 31xC and 312 IFM, because these cannot be
operated ungrounded.
S7-300 Programmable Controller Hardware and Installation
A5E00105492-02
Configuring
5-27

Advertisement

Table of Contents
loading

Table of Contents