Siemens SIMATIC S7-300 Hardware And Installation Manual page 224

Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Appendix
Table 12-8
High-voltage protection of cables with surge voltage protection omponents
Consec.
Cables for ...
no.
1
3-phase TN-C system
3-phase TN-S system
3-phase TT system
AC TN-S system
AC TN-C system
AC TT system
2
24 VDC Power Supply
3
MPI bus cable, RS485, RS232
(V.24)
4
Inputs/outputs of digital modules
24 V
5
24 VDC power supply module
6
Inputs/outputs of digital modules
and 120/230 VAC power supply
7
Inputs/outputs of analog modules
up to 12 V +/-
* You can order these components directly from:
DEHN + SÖHNE
GmbH + Co. KG
Elektrotechnische Fabrik
Hans-Dehn-Str. 1
D-92318 Neumarkt
12-22
... equip transition point 0 <-> 1
with:
1 x
DEHNbloc/3
lightning conductor, phase
L1/L2/L3 to PEN
1 x
DEHNbloc/3
lightning conductor, phase
L1/L2/L3 to PE
1 x
DEHNbloc/1
lightning conductor, N to PE
1 x
DEHNbloc/3
lightning conductor, phase
L1/L2/L3 to N
1 x
DEHNgap B/n
N-PE lightning conductor, N
to PE
2 x
DEHNbloc/1
lightning conductor, phase
L1 +N to PE
1 x
DEHNbloc/1
lightning conductor, phase L
to PEN
1 x
DEHNbloc/1
lightning conductor, phase
to N
1 x
DEHNgap B/n
N-PE lightning conductor, N
to PE
1 x
Blitzductor VT Lightning
conductor,
type A D 24 V -
1 x
Blitzductor CT lightning
conductor, type B
DEHNrail 24 FML
1 x
Blitzductor VT
lightning conductor, type AD
24 V -
2 x
DEHNbloc/1 lightning
conductor
1 x
Blitzductor CT lightning
conductor, type B
S7-300 Programmable Controller Hardware and Installation
Order No.
900 110*
5SD7 031
900 110*
5SD7 031
900 111*
5SD7 032
900 110*
5SD7 031
900 130*
900 111*
5SD7 032
900 111*
5SD7 032
900 111*
5SD7 032
900 130*
918 402*
919 506* and
919 510*
909 104*
918 402*
900 111*
5SD7 032
900 111*
5SD7 032
919 506* and
919 510*
A5E00105492-02