5.8.4 Isolated or non-isolated modules?

Isolated modules
In configurations with isolated modules, the reference potentials of the control
circuit (M
internal
Application
Use isolated modules for:
• All AC load circuits
• DC load circuits with separate reference potential
Examples:
DC load circuits whose sensors have different reference potentials (for
example if grounded sensors are located at some considerable distance
from the control system and no equipotential bonding is possible)
DC load circuits with grounded positive pole (L+) (battery circuits).
Isolated modules and grounding concept
You can use isolated modules, regardless of whether or not the control system's
reference potential is grounded.
S7-300 Programmable Controller Hardware and Installation
A5E00105492-02
) and load circuit (M
external
) are electrically isolated (see Figure).
Configuring
5-23