Temperature Rise Completion Range Setting (Buffer Memory Address: A7 H ); Temperature Rise Completion Soak Time Setting (Buffer Memory Address: A8 H ); Pid Continuation Flag (Buffer Memory Address: A9 H ); Heater Disconnection Compensation Function Selection (Buffer Memory Address: Aa H ) - Mitsubishi Electric MELSECSystem Q User Manual

Q64tctt;q64tcttbw; q64tcrt;q64tcrtbw
Table of Contents

Advertisement

3 SPECIFICATIONS
3.5.39 Temperature rise completion range setting (buffer memory address: A7
3.5.40 Temperature rise completion soak time setting (buffer memory address: A8
3.5.41 PID continuation flag (buffer memory address: A9
3.5.42 Heater disconnection compensation function selection (buffer memory address: AA
3.5.43 Transistor ON delay output delay time setting (buffer memory address: AF
3 - 45
(1) Sets the temperature rise/fall values, at which a temperature rise will be judged as
completed, relative to the set value.
Temperature rise
completion range (+)
Set value (SV)
Temperature rise
completion range (-)
(2) The setting range is 1 to 10°C.
(1) Sets a delay from when a temperature rise is completed until the temperature rise
completion judgment flag is turned on (1).
(2) The setting range is 0 to 3600 (min).
(1) Sets the operation mode to be entered when the setting mode/operation mode
command (Yn1) turns off.
• 0: Stop (default)
• 1: Continue
(2) Refer to Section 3.2.13 for the control status governed by ON/OFF of the PID
continuation flag.
Sets whether the heater disconnection compensation function (refer to Section 3.2.7) is
used or not.
• 0: Heater disconnection compensation function is not used (default)
• 1: Heater disconnection compensation function is used
(1) Make this setting to delay the timing when the transistor output monitor (buffer
memory address: b8 of 15
Set this when performing heater disconnection detection using the input module.
(2) The setting range is 0 and 1 to 50 (10 to 500ms).
When the setting is 0, the transistor output flag (buffer memory address: b8 of 15
to 18
) does not turn on (1).
H
)
H
to 18
) turns on.
H
H
MELSEC-Q
)
H
Temperature rise
judgment range
)
H
)
H
)
H
H
3 - 45