Bfm #79: Temperature Rise Completion Range Setting; Bfm #80: Temperature Rise Completion Soak Time - Mitsubishi Electric MELSEC FX2N-2LC User Manual

Temperature control block
Hide thumbs Also See for MELSEC FX2N-2LC:
Table of Contents

Advertisement

FX2N-2LC Temperature Control Block
7.2.38

BFM #79: Temperature rise completion range setting

In BFM #79, set the temperature rise completion range. This setting is applied to both CH1
and CH2.
Set the temperature range in which the temperature rise completion range is judged based on
the temperature set value.
The actual temperature rise completion range is judged within the range above and below the
temperature set value, so the range width is twice.
Set value (SV)
Temperature
rise completion
7.2.39

BFM #80: Temperature rise completion soak time

In BFM #80, set the temperature rise completion soak time. This setting is applied to both CH1
and CH2.
The temperature rise completion soak time is the period of time after the measured value
reaches the temperature rise completion range until the temperature rise completion flag turns
on.
In order to cope with a case in which the measured value has reached the temperature rise
completion range but is not stable yet, by setting the soak time, the wait time can be set for
judgement on temperature rise completion.
Example 1: When the soak time is set to "0"
Set value (SV)
Temperature
rise completion
Example 2: When the soak time is set to any positive value
Set value (SV)
Temperature
rise completion
Soak
Soak
time
time
Buffer Memory (BFM) 7
Temperature rise
completion range
Temperature rise
completion range
Temperature rise
completion range
7