Siemens simatic hmi op27 Equipment Manual page 209

Operator panels
Table of Contents

Advertisement

System Messages
Message
Cause
200
Battery power no longer sufficient for internal data buffer
on OP.
Battery on memory is discharged, data may no longer be
readable.
210
Internal error
OP co-ordination area not receivable during startup.
212
Internal error
Bit for changing operating mode has been inverted erro-
neously.
213
Offline mode not possible at present.
214
The job number sent by the PLC or configured in a func-
tion field is too large.
217, 218
Overlapping specified/actual values.
230
The minimum value is greater than the maximum value
for variable limits.
231
The minimum value is equal to the maximum value for
variable scales.
250
You can not switch to the desired operating mode.
251
Error transferring data record to PLC.
252
Function can not be executed as a function of the same
group has not yet been completed (e.g.: setpoint entry is
active, password list can not be opened).
253
Access to data medium is not possible.
254
The disk must be formatted before a data record can be
saved for the first time.
255
Not enough space on disk for this data record.
256
Not enough system memory available to execute the de-
sired function.
257
Data record has been stored with a different version
stamp than defined in the current configuration.
258
A parameter record has been selected as a recipe. Param-
eter records can not be edited directly.
D-4
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Remedy:
Replace battery.
Note:
Replace the battery while the unit is
switched on in order to prevent loss of
data.
Press restart button.
Restart OP.
Try change of operating mode again later.
Check PLC program and configured
screen.
Check configuration of actual/specified
values in the process link.
Correct the limit settings.
Correct the scale on the OP.
Check parameters of PLC job.
Check recipe configuration.
Wait until preceding function has been
completed (or terminate function) and then
invoke desired function again.
1. Floppy drive not present,
2. Floppy is read only,
3. Disk is not formatted.
First format the disk.
Delete data records that are no longer re-
quired.
Try activating function again. Check con-
figuration.
1. Move function to a different screen
2. Simplify screen structure
3. Do not use trends on screen in conjunc-
tion with this function
If the data records are to continue to be
used, the old version number must be en-
tered in the recipe configuration.
Caution:
The structure of the recipe determines the
assignment of data to a data record.
Only individual data records of a parameter
record can be edited.
OP27, OP37 Equipment Manual
Release 05/99