Verify Configuration - Emerson Rosemount 3051 Series Quick Start Manual

Pressure transmitters and flowmeters with 4-20 ma hart and 1-5 vdc low power protocol
Hide thumbs Also See for Rosemount 3051 Series:
Table of Contents

Advertisement

September 2016
Figure 9. Load Limitation
Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5)
1387
1000
500
0
10.5
Communication requires a minimumloop resistance of 250 ohms.
1. For CSA approval, power supply must not exceed 42.4 V.
The total resistance load is the sum of the resistance of the signal leads and the
load resistance of the controller, indicator, and related pieces. Note that the
resistance of intrinsic safety barriers, if used, must be included.
4.3 Power supply for 1–5 Vdc HART Low Power
Low power transmitters operate on 6–12 Vdc. The dc power supply should
provide power with less than two percent ripple. The V
or greater.

5.0 Verify configuration

5.1 Field Communicator user interface
The Traditional Interface - Device Revision 3 and DD Revision 2 Fast Key sequence
can be found on
Figure 10. Traditional Interface - Device Revision 3 and DD Revision 2
3051:PT 93207
Online
1 Device setup
2 PV
3 Analog Output
4 PV LRV
5 PV URV
The Device Dashboard - Device Revision 3 and DD Revision 6 Fast Key sequence
can be found on
Operating
Region
30
20
(1)
42.4
Voltage (Vdc)
page
12.
0.00 mbar
4.000 mA
0.00 mbar
370.00 mbar
SAVE
page
12.
Quick Start Guide
load should be 100 kW
out
11