4-4-55 Option setting error of outdoor unit

Outdoor Unit Display
Indoor Unit Display
Judgment Method
Special Cause
1. How to check
Is the Compressor breakdown
setting value is "not set"?
Is the outdoor unit EEPROM accurately
connected to connector?
Download relevant model EEPROM and then reset.
※ Execute automatic commissioning for UP
cancellation after EEPROM download.
Samsung Electronics
(Operation) ×(Reservation)
(There is No Compressor start in a Unit because of Compressor Cut off Option Setting. )
Yes
Yes
(Blast) ×(Filter) ×(Defrost)
Set the compressor breakdown setting
value as "not set"
No
※ When There is No Compressor start in a Unit
because of Compressor Cut off Option
Setting, E560.
No
Connect outdoor unit EEPROM and then reset.
Troubleshooting
4-115