4-3-43. Option setting error of outdoor unit

Inverter / Hydro control part display
Judgment Method
Cause of problem
1. Inspection Method
Is the Compressor breakdown
setting value is "not set"?
Is the outdoor unit EEPROM accurately connected to
connector?
Download relevant model EEPROM and then reset.
Refer to the inspection method below.
∙ Option setting error of outdoor unit.
(E2P option use of other model or set of the relevant outdoor unit, compressor breakdown)
Yes
Yes
Set the compressor breakdown setting value as "not set"
No
※ When setting breakdown for repair and replace of
compressor : Change the setting after replace.
No
Connect outdoor unit EEPROM and then reset.
88