Danfoss VLT Micro Drive Quick Manual page 20

Hide thumbs Also See for VLT Micro Drive:
Table of Contents

Advertisement

Quick Guide
1.7.3 Line Power Supply 3x380–480 V AC
Normal overload 150% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW]
Typical Shaft Output [HP]
IP 20
Output current
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous (3x440–480 V) [A]
Intermittent (3x440–480 V) [A]
Max. cable size:
(line power, motor) [mm
Max. input current
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous (3x440–480 V) [A]
Intermittent (3x440–480 V) [A]
Max. electrical fuses [A]
Environment
Estimated power loss hp [W], Best case/
1)
Typical
Weight enclosure IP20 (lb [kg])
Efficiency [%], Best case/
Typical
1)
Table 1.15 Line Power Supply 3x380–480 V AC
1.
At rated load conditions.
®
VLT
Micro Drive Quick Guide
PK37
0.37
0.5
Frame
M1
1.2
1.8
1.1
1.7
2
/AWG]
1.9
2.6
1.7
2.3
0.025
[18.5]/
0.034
[25.5]
2.43 [1.1]
96.8/
95.5
®
MG02B722 - VLT
is a registered Danfoss trademark
PK75
P1K5
P2K2
0.75
1.5
2.2
1
2
3
Frame
Frame
Frame
M1
M2
M2
2.2
3.7
5.3
3.3
5.6
8.0
2.1
3.4
4.8
3.2
5.1
7.2
4/10
3.5
5.9
8.5
4.7
8.7
12.6
3.0
5.1
7.3
4.0
7.5
10.8
See 1.3.4 Fuses
0.038
0.056
0.077
[28.5]/
[41.5]/
[57.5]/
0.058
0.076
0.109
[43.5]
[56.5]
[81.5]
2.43 [1.1]
3.53 [1.6]
3.53 [1.6]
97.4/
98.0/
97.9/
96.0
97.2
97.1
1
P3K0
P4K0
3.0
4.0
4
5
Frame
Frame
M3
M3
7.2
9.0
10.8
13.7
6.3
8.2
9.5
12.3
11.5
14.4
16.8
20.2
9.9
12.4
14.4
17.5
0.101
0.132
[75.0]/
[98.5]/
0.136
0.179
[101.6]
[133.5]
6.6 [3.0]
6.6 [3.0]
98.0/
98.0/
97.2
97.3