Vega VEGABAR 17 Operating Instructions Manual page 14

Process pressure transmitter with metallic measuring cell
Table of Contents

Advertisement

5 Connecting to power supply
Connecting through
terminal housing
14
1
Fig. 6: Connection to the screw terminals
1
Cable gland
2
Cover
3
Plug housing
4
Plug insert
5
Plug seal
8. Snap the plug insert into the plug housing and insert the sensor
seal
Information:
Note the correct arrangement, see illustration
9. Tighten the screws on the strain relief and cable entry
10. Hook in the cover and push onto the plug connection, tighten
cover screw
11. Plug the plug insert with seal to VEGABAR 17 and tighten the
screw
The electrical connection is finished.
Proceed as follows:
1. Screw on the housing cover
2. Loosen the cable gland with an open-end wrench SW 24
3. Remove approx. 5 cm of the cable mantle, strip approx. 1 cm
insulation from the individual wires
4. Lead the cable through the cable gland into the plug housing
5. Press down the plastic lever on the respective spring terminal
block with a screwdriver, so that the terminal contact opens
6. Insert the confectioned cable end into the opening
7. Release the plastic lever so that the cable end is clamped in the
terminal block
8. After connecting the individual cores, tighten the cable gland and
screw on the housing cover
The electrical connection is finished.
2
3
4
5