Vega VEGABAR 82 Operating Instructions Manual

Vega VEGABAR 82 Operating Instructions Manual

Modbus and levelmaster protocol, pressure transmitter with ceramic measuring cell
Hide thumbs Also See for VEGABAR 82:
Table of Contents

Advertisement

Operating Instructions

Pressure transmitter with ceramic
measuring cell
VEGABAR 82
Modbus and Levelmaster protocol
Document ID: 46294

Advertisement

Table of Contents
loading

Summary of Contents for Vega VEGABAR 82

  • Page 1: Operating Instructions

    Operating Instructions Pressure transmitter with ceramic measuring cell VEGABAR 82 Modbus and Levelmaster protocol Document ID: 46294...
  • Page 2: Table Of Contents

    Setting up sensor and Modbus interface with PACTware ..........48 Connect the PC ......................48 Parameter adjustment ....................49 Set instrument address ....................51 Diagnosis, asset management and service ................ 52 Maintenance ........................52 VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 3 10.11 Trademark ........................100 Safety instructions for Ex areas Take note of the Ex specific safety instructions for Ex applications. These instructions are attached as documents to each instrument with Ex approval and are part of the operating instructions manual. Editing status: 2017-11-14 VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 4: About This Document

    Symbols used Document ID This symbol on the front page of this instruction refers to the Docu- ment ID. By entering the Document ID on www.vega.com you will reach the document download. Information, tip, note This symbol indicates helpful additional information.
  • Page 5: For Your Safety

    During work on and with the device the required personal protective equipment must always be worn. Appropriate use The VEGABAR 82 is a pressure transmitter for process pressure and hydrostatic level measurement. You can find detailed information about the area of application in chapter "Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.
  • Page 6: Eu Conformity

    For further information see www.namur.de. Installation and operation in the USA and Canada This information is only valid for USA and Canada. Hence the follow- ing text is only available in the English language. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 7: Environmental Instructions

    That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: • Chapter "Packaging, transport and storage" • Chapter "Disposal" VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 8: Product Description

    Alternatively, you can access the data via your smartphone: • Download the VEGA Tools app from the "Apple App Store" or the "Google Play Store" • Scan the Data Matrix code on the type label of the instrument or •...
  • Page 9: Principle Of Operation

    Optional instrument features are also described in this operating instructions manual. The respective scope of delivery results from the order specification. Principle of operation The VEGABAR 82 is suitable for the measurement of the following Measured variables process variables: • Process pressure •...
  • Page 10 3 Product description Fig. 3: Process pressure measurement VEGABAR 82 Application area VEGABAR 82 is suitable for applications in virtually all industries. It is used for the measurement of the following pressure types. • Gauge pressure • Absolute pressure •...
  • Page 11 Recessed installation The recessed installation is particularly suitable for applications with gases, vapours and clear liquids. The measuring cell seal is posi- tioned laterally as well as in addition in front. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 12 Fig. 6: Front-flush installation of the measuring cell (example: thread G1½) Seal for the process fitting Measuring cell Seal for the measuring cell Process fitting Diaphragm Completely front-flush The completely front-flush mounting is particularly suitable for ap- mounting with single seal plications in the paper industry. The diaphragm is in the pulp flow, is hence cleaned and protected against buildup. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 13 Additional, front seal for measuring cell Diaphragm Installation in hygienic The front-flush, hygienic installation of the measuring cell is particu- fitting larly suitable for food applications. The sealings are installed gap-free. The form seal of the measuring cell protects also the glass joint. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 14: Supplementary Cleaning Procedures

    Diaphragm Hole for leakage detection Supplementary cleaning procedures The VEGABAR 82 is also available in the version "Oil, grease and silicone-free". These instruments have passed through a special cleaning procedure to remove oil, grease and paint-wetting impair- ment substances (PWIS).
  • Page 15: Packaging, Transport And Storage

    3 Product description Caution: The VEGABAR 82 in this version may not be used in oxygen ap- plications. For this purpose, instruments are available in the special version "Oil and grease-free for oxygen applications". Packaging, transport and storage Packaging Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test based on ISO 4180.
  • Page 16 You can find further information in the operating instructions "Elec- tronics module VEGABAR series 80" (Document-ID 45054). Supplementary electron- The supplementary electronics is a replacement part for sensors with ics for Modbus signal output Modbus. You can find further information in the operating instructions "Supple- mentary electronics for Modbus" (Document-ID 41864). VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 17: Mounting

    The free openings for the cable glands are therefore covered with red dust protection caps as transport protection. The dust protection caps do not provide sufficient protection against moisture. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 18: Ventilation And Pressure Compensation

    Ventilation and pressure compensation are carried out with VEGABAR 82 via a filter element. It is air permeable and moisture- blocking. Caution: The filter element causes a time-delayed pressure compensation. When quickly opening/closing the housing cover, the measured value can change for approx. 5 s by up to 15 mbar. For effective ventilation, the filter element must always be free of buildup. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 19 • Instruments with absolute pressure Instruments in Ex-d ver- The filter element is integrated in the process assembly. It is located in sion a rotatable metal ring and has the following function: • Atmospheric pressure compensation (with relative pressure meas- uring ranges) VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 20 The filter element is mounted into the electronics housing. It has the following functions: • Ventilation of the electronics housing • Atmospheric pressure compensation (with relative pressure meas- uring ranges) → Turn the housing so that the filter element points downward after the instrument is installed. This provides better protection against buildup. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 21: Process Pressure Measurement

    Measurement setup in Keep the following in mind when setting up the measuring system: vapours • Connect via a siphon • Do not insulate the siphon • Fill the siphon with water before setup VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 22 < 100 °C on the transmitter is ensured. Measurement setup in Keep the following in mind when setting up the measuring system: liquids • Mount the instrument below the measuring point The effective pressure line is always filled with liquid and gas bubbles can bubble up to the process line. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 23: Level Measurement

    • Mount the instrument below the min. level • Do not mount the instrument close to the filling stream or emptying area • Mount the instrument so that it is protected against pressure shocks from the stirrer Fig. 18: Measurement setup for level measurement VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 24: External Housing

    1. Mark the holes according to the following drilling template 2. Fasten wall mounting plate with 4 screws 90 mm (3.54") 70 mm (2.76") 8 mm (0.12") (0.32") Fig. 20: Drilling template - wall mounting plate VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 25: Connecting To Power Supply And Bus System

    On plastic housings, the NPT cable gland or the Conduit steel tube must be screwed into the threaded insert without grease. Max. torque for all housings, see chapter "Technical data". VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 26: Connecting

    4. Insert the cable into the sensor through the cable entry Fig. 21: Connection steps 5 and 6 5. Insert the wire ends into the terminals according to the wiring plan VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 27: Wiring Plan

    When inserting the terminal block again, you should hear it snap in. Wiring plan Overview Fig. 22: Position of connection compartment (Modbus electronics) and electron- ics compartment (sensor electronics) Terminal compartment Electronics compartment VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 28 Slide switch for integrated termination resistor (120 Ω) Modbus signal Voltage supply Terminal Function Polarity Voltage supply Voltage supply Modbus signal D0 Modbus signal D1 Function ground when installing ac- cording to CSA (Canadian Standards Association) VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 29: External Housing With Version Ip 68 (25 Bar)

    5 Connecting to power supply and bus system External housing with version IP 68 (25 bar) Overview Fig. 25: VEGABAR 82 in IP 68 version 25 bar with axial cable outlet, external housing Electronics and connec- tion compartment for power supply 4...20mA...
  • Page 30 Fig. 28: Terminal compartment USB interface Slide switch for integrated termination resistor (120 Ω) Modbus signal Voltage supply Terminal Function Polarity Voltage supply Voltage supply Modbus signal D0 Modbus signal D1 VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 31: Switch-On Phase

    Output signal at instruments with current output jumps to the set fault current Then the actual measured value is outputted to the signal cable. The value takes into account settings that have already been carried out, e.g. default setting. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 32: Set Up The Sensor With The Display And Adjustment Module

    The display and adjustment module is powered by the sensor, an ad- ditional connection is not necessary. Fig. 29: Insertion of the display and adjustment module Note: If you intend to retrofit the instrument with a display and adjustment module for continuous measured value indication, a higher lid with an inspection glass is required. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 33: Adjustment System

    The pen oper- ates the four keys of the display and adjustment module right through the closed lid (with inspection window) of the sensor housing. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 34: Measured Value Indication

    In the third view, the selected measured value as well as a second selectable value, e.g. the temperature, are displayed. With the "OK" key you move (during the initial setup of the instrument) to the selection menu "Language". VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 35: Parameter Adjustment - Quick Setup

    For technically demanding measuring points, you can carry out extended settings in "Extended adjustment". The main menu is divided into five sections with the following func- Main menu tions: Setup: Settings, e.g., for measurement loop name, application, units, position correction, adjustment, signal output Display: Settings, e.g., for language, measured value display, lighting VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 36 Setup - Application In this menu item you activate/deactivate the slave sensor for elec- tronic differential pressure and select the application. VEGABAR 82 can be used for process pressure and level measure- ment. Default setting is process pressure measurement. The mode can be changed in this adjustment menu.
  • Page 37 20 % of the nominal measuring range, then no position correction is possible. Setup - Adjustment VEGABAR 82 always measures pressure independently of the pro- cess variable selected in the menu item "Application". To output the VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 38 1. Select the menu item "Setup" with [->] and confirm with [OK]. Now select with [->] the menu item "Zero adjustment" and confirm with [OK]. 2. Edit the mbar value with [OK] and set the cursor to the requested position with [->]. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 39 [OK]. The span adjustment is finished. Setup - Min. adjustment Proceed as follows: Level 1. Select the menu item "Setup" with [->] and confirm with [OK]. Now select with [->] the menu item "Adjustment", then "Min. adjustment" and confirm with [OK]. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 40 - and the indication or output of the volume is required. Corresponding linearization curves are preprogrammed for these vessels. They represent the correlation between the level per- centage and vessel volume. The linearization applies to the measured value indication and the current output. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 41 This menu item enables the setting of the requested national lan- guage. The following languages are available: • German • English • French • Spanish • Russian • Italian • Dutch • Portuguese • Japanese • Chinese • Polish • Czech • Turkish VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 42 6 Set up the sensor with the display and adjustment module In delivery status, the VEGABAR 82 is set to English. Display - Displayed value In this menu item, you define which measured value is displayed. 1 and 2 The default setting for the display value is "Lin. percent". Display - Display format...
  • Page 43 Additional settings - After a reset, certain parameter adjustments made by the user are Reset reset. The following reset functions are available: Delivery status: Restores the parameter settings at the time of shipment from the factory, incl. the order-specific settings. Any user- VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 44 Number of positions after the decimal point, automatically Backlight Switched on Reset - Diagnosis Menu item Parameter Default value Sensor status Pressure Actual measured value Peak value Temperature Actual temperature values from measuring cell, elec- tronics VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 45 The data are saved only after release. Additional settings - Spe- In this menu item you gain access to the protected area where cial parameters you can enter special parameters. In exceptional cases, individual parameters can be modified in order to adapt the sensor to special requirements. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 46 PC. In this menu item, the features of the sensor such as approval, pro- Info - Sensor character- istics cess fitting, seal, measuring range, electronics, housing and others are displayed. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 47: Saving The Parameterisation Data

    If it is necessary to exchange a sensor, the display and adjustment module is inserted into the replacement instrument and the data are likewise written into the sensor via the menu item "Copy device settings". VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 48: Setting Up Sensor And Modbus Interface With Pactware

    Interface adapter VEGACONNECT Sensor To the Modbus electron- Connection of the PC to the Modbus electronics is carried out via a USB cable. Scope of the parameter adjustment: • Sensor electronics • Modbus electronics VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 49: Parameter Adjustment

    For parameter adjustment of the instrument via a Windows PC, the configuration software PACTware and a suitable instrument driver (DTM) according to FDT standard are required. The latest PACTware version as well as all available DTMs are compiled in a DTM Collec- VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 50 The standard version is available as a download under www.vega.com/downloads and "Software". The full version is avail- able on CD from the agency serving you. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 51: Set Instrument Address

    7 Setting up sensor and Modbus interface with PACTware Set instrument address The VEGABAR 82 requires an address for participating as a Slave in the Modbus communication. The addess setting is carried out via a PC with PACTware/DTM or Modbus RTU.
  • Page 52: Diagnosis, Asset Management And Service

    Overview The hygienic connection with compression nut can be disassembled and the diaphragm cleaned. The following graphic shows the structure: Fig. 37: VEGABAR 82, structure of the hygienic connection with compression Hexagon Compression nut Process fitting Process module...
  • Page 53: Diagnosis Memory

    Asset Management function The instrument features self-monitoring and diagnostics according to NE 107 and VDI/VDE 2650. In addition to the status messages in the following tables, detailed error messages are available under menu VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 54 State in CMD 48 • • F013 Gauge pressure or low pressure Exchange measuring cell Bit 0 of Byte 0 … 5 • • Measuring cell defective Send instrument for repair No valid measured value available VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 55 • • F265 Sensor no longer carries out a Carry out a reset Bit 13 of Byte 0 … 5 • measurement Disconnect operating voltage Measurement func- briefly tion disturbed VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 56 • • M507 Error during setup Carry out reset and repeat Bit 4 of • Error when carrying out a reset setup Byte 14 … 24 Error in the instru- ment settings VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 57: Rectify Faults

    24 hour service hotline Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550. The hotline is also available outside normal working hours, seven days a week around the clock.
  • Page 58: Exchanging The Electronics Module

    8 Diagnosis, asset management and service Fig. 39: VEGABAR 82 in IP 68 version, 25 bar and lateral cable outlet, external housing Process module Plug connector Fixing screw Cable assembly Connection cable External housing 3. Loosen the plug connector 4. Mount the new process module on the measuring point 5.
  • Page 59: Software Update

    Clean the instrument and pack it damage-proof • Attach the completed form and, if need be, also a safety data sheet outside on the packaging • Please contact the agency serving you to get the address for the return shipment. You can find the agency on our home page www.vega.com. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 60: Dismount

    Pass the instrument directly on to a spe- cialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 61: Supplement

    Ʋ Sealing, cable gland Ʋ Blind plug, cable gland Ʋ Seal between housing and housing lid Silicone SI 850 R, NBR silicone-free Ʋ Inspection window in housing cover Polycarbonate, UL746-C listed (with Ex-d version: glass) VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 62 Ʋ Plastic housing 10 Nm (7.376 lbf ft) Ʋ Aluminium/Stainless steel housing 50 Nm (36.88 lbf ft) Input variable The specifications are only an overview and refer to the measuring cell. Limitations due to the material and version of the process fitting as well as the selected pressure type are possible. The specifications on the nameplate apply. Between transmitter and external electronics housing. Fix connected to the sensor. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 63 200 bar/20000 kPa 0 bar abs. (only for measuring cell ø 28 mm) Nominal measuring ranges and overload capacity in psi Nominal range Overload capacity, max. pressure Overload capacity, min. pressure Gauge pressure VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 64 0 … 300 psi 1500 psi 0 psi 0 … 900 psi +2900 psig 0 psi 0 … +1450 psig 2900 psig 0 psi (only for measuring cell ø 28 mm) Adjustment ranges Specifications refer to the nominal measuring range, pressure values lower than -1 bar cannot be VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 65 : dead time; t : rise time; t : jump response time Process variable Output signal VEGABAR 82 VEGABAR 82 - IP 68 (25 bar) Dead time ≤ 25 ms ≤ 50 ms Rise time (10 … 90 %) ≤ 55 ms ≤ 150 ms Step response time (ti: 0 s, 10 … 90 %) ≤ 80 ms...
  • Page 66 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio "nominal measuring range/set span". The thermal change of the zero signal and output span corresponds to the temperature error F chapter "Calculation of the total deviation (according to DIN 16086)". Basic temperature error F VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 67 TD 10 : 1 TD 20 : 1 Factor FTD 1.75 10.5 Long-term stability (according to DIN 16086) Applies to the respective digital signal output (e.g. HART, Profibus PA) as well as to analogue cur- rent output 4 … 20 mA under reference conditions. Specifications refer to the set span. Turn down (TD) is the ratio nominal measuring range/set span. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 68: Ambient Conditions

    -20 … +80 °C (-4 … +176 °F) tion cable PUR Version IP 68 (25 bar), connection -20 … +60 °C (-4 … +140 °F) -20 … +60 °C (-4 … +140 °F) cable PE VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 69 130 °C 100 °C -40 °C (266 °F) (212 °F) (-104 °F) -40 °C (-104 °F) Fig. 42: Temperature derating VEGABAR 82, version up to +130 °C (+266 °F) Process temperature Ambient temperature With process fitting PVDF, process temperature max. 100 °C (212 °F). VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 70 -40 °C (212 °F) (302 °F) (-104 °F) -40 °C (-104 °F) Fig. 43: Temperature derating VEGABAR 82, version up to +150 °C (+302 °F) Process temperature Ambient temperature SIP process temperature (SIP = Sterilization in place) Applies to instruments configurations suitable for vapour, i.e. material measuring cell seal EPDM or FFKM (Perlast G75S).
  • Page 71 W x H = 7 x 13 mm Adjustment elements Ʋ 4 keys [OK], [->], [+], [ESC] Ʋ Switch Bluetooth On/Off Bluetooth interface Ʋ Standard Bluetooth smart Ʋ Effective range 25 m (82.02 ft) Breather capillaries not with Ex-d version. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 72 < 500 mW Reverse voltage protection Integrated Potential connections and electrical separating measures in the instrument Electronics Not non-floating Ground terminal Galvanically connected with the metal process fitting Galvanic separation between electronics and metal housing parts Ʋ Reference voltage 500 V AC VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 73: Basics Modbus

    Instruments with approvals can have different technical specifications depending on the version. For that reason the associated approval documents of these instruments have to be carefully noted. They are part of the delivery or can be downloaded under www.vega.com, "Instrument search (serial number)" as well as in the download area. 10.2 Basics Modbus Bus description The Modbus protocol is a communication protocol for the communication between instruments.
  • Page 74 Fig. 44: Bus architecture Modbus Connection resistor Bus participant Voltage supply Protocol description The VEGABAR 82 is suitable for connection to the following RTUs with Modbus RTU or ASCII protocol. Protocol ABB Totalflow Modbus RTU, ASCII Bristol ControlWaveMicro Modbus RTU, ASCII...
  • Page 75: Modbus Register

    (4 bytes) according to IEEE 754 are transmitted with individually selectable order of the data bytes (byte transmission order). This "Byte transmission order" is determined in the parameter "Format Code". Hence the RTU knows the registers of the VEGABAR 82 which must be contacted for the variables and status information.
  • Page 76 Primary Variable in Byte Order BACD (Middle Endian) 2204 DWord Secondary Variable in Byte Order BACD (Middle Endian) 2206 DWord Third Variable in Byte Order BACD (Middle Endian) 2208 DWord Quarternary Variable in Byte Order BACD (Middle Endian) VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 77: Modbus Rtu Commands

    FC4 Read Input Register With this command, any number (1-127) of input registers can be read out. The start register, from which the readout should start, and the number of registers are transmitted. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 78 2 Bytes Data FC8 Diagnostics With this function code different diagnostic functions can be triggered or diagnostic values read out. Request: Parameter Length Code/Data Function Code 1 Byte 0x08 Sub Function Code 2 Bytes Data N*2 Bytes Data Response: Parameter Length Code/Data Function Code 1 Byte 0x08 VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 79 0x01 to 0x7B FC17 Report Slave ID With this function code, the Slave ID can be queried. Request: Parameter Length Code/Data Function Code 1 Byte 0x11 Response: Parameter Length Code/Data Function Code 1 Byte 0x11 VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 80: Levelmaster Commands

    List of Object value 1 Byte Depending on the Object ID 10.5 Levelmaster commands The VEGABAR 82 is also suitable for connection to the following RTUs with Levelmaster protocol. The Levelmaster protocol is often called "Siemens" "Tank protocol". Protocol ABB Totalflow...
  • Page 81 25.4 m). If the temperature should be transmitted in the Levelmaster protocol, then TV must be set in the sensor to temperature. PV, SV and TV can be adjusted via the sensor DTM. VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 82 Code/Data Set Baud Rate 8 (12) characters ASCII UuuBbbbb[b][pds] Bbbbb[b] = 1200, 9600 (default) pds = parity, data length, stop bit (optional) parity: none = 81, even = 71 (default), odd = 71 VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 83 Report Receive to Transmit Delay 4 characters ASCII UuuR Response: Parameter Length Code/Data Report Receive to Trans- 7 characters ASCII UuuRmmm mit Delay mmm = milliseconds (50 up to 250), default = 127 ms VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 84: Configuration Of Typical Modbus Hosts

    Value out of limits 10.6 Configuration of typical Modbus hosts Fisher ROC 809 Wiring plan (Rx/Tx -) (Rx/Tx +) +30 Vdc Fig. 45: Connection of VEGABAR 82 to RTU Fisher ROC 809 VEGABAR 82 RTU Fisher ROC 809 Voltage supply Parameter Parameter Value Baud Rate...
  • Page 85 10 Supplement ABB Total Flow Wiring plan Bus + Bus - VBAT Fig. 46: Connection of VEGABAR 82 to RTU ABB Total Flow VEGABAR 82 RTU ABB Total Flow Parameter Parameter Value Baud Rate 9600 Floating Point Format Code RTU Data Type...
  • Page 86 10 Supplement Thermo Electron Autopilot Wiring plan Rx - +30 Vdc Fig. 47: Connection of VEGABAR 82 to RTU Thermo Electron Autopilot VEGABAR 82 RTU Thermo Electron Autopilot Voltage supply Parameter Parameter Value Baud Rate 9600 Floating Point Format Code...
  • Page 87 3 TX- 4 GND 5 RXT 6 TXT 7 not used 8 not used +30 Vdc Fig. 48: Connection of VEGABAR 82 to RTU Bristol ControlWave Micro VEGABAR 82 RTU Bristol ControlWave Micro Voltage supply Parameter Parameter Value Baud Rate...
  • Page 88: Calculation Of The Total Deviation

    10 Supplement ScadaPack Wiring plan COM Part 3 (C3) RS485 TXD- TXD+ +30 Vdc Fig. 49: Connection of VEGABAR 82 to RTU ScadaPack VEGABAR 82 RTU ScadaPack Voltage supply Parameter Parameter Value Baud Rate 9600 Floating Point Format Code RTU Data Type...
  • Page 89: Practical Example

    1. Calculation of the Turn down TD = 10 bar/4 bar, TD = 2.5 : 1 2. Determination temperature error F Fig. 50: Determination of the basic temperature error for the above example: F = 0.15 % TBasis VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 90 = 0.79 % = 0.2 % = √(0.79 %) + (0.2 %) perf = 0.81 % perf 2. step: Total deviation F total total perf stab = 0.81 % (result of step 1) perf VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 91: Dimensions

    10.9 Dimensions The following dimensional drawings represent only an extract of the possible versions. Detailed dimensional drawings can be downloaded at www.vega.com under "Downloads" and "Drawings". The instrument versions are shown with single chamber housing, however are designed with the...
  • Page 92 (4.33" x 3.54") ~ 66 mm (2.60") 110 mm x 90 mm (4.33" x 3.54") Fig. 52: VEGABAR 82, IP 68 version with external housing Lateral cable outlet Axial cable outlet Plastic single chamber Stainless steel single chamber Seal 2 mm (0.079 in), (only with 3A approval)
  • Page 93 ø 6 mm ø 6 mm ( 0.24 ") ( 0.24 ") Fig. 53: VEGABAR 82, threaded fitting not front-flush DU G½, EN 837; manometer connection DI G½, inside G¼, ISO 228-1 DQ G½, inside G¼ A, ISO 228-1, PVDF DD G½, EN 837;...
  • Page 94 ø 55 mm ø 55 mm ø 60 mm (2.17") (2.17") (2.36") Fig. 54: VEGABAR 82, threaded fitting front-flush C3 G½, ISO 228-1; frontbündig N9 G¾, DIN 3852-E C5 G1, ISO 228-1 DA G1½, DIN 3852-A DV G1½, DIN 3852-A-B, PVDF C9 1½...
  • Page 95 For the version with temperature range up to 150 °C/302 °F, the measure of length increases by 28 mm (1.1 in). For the version with "Second Line of Defense", the measure of length increases by 17 mm (0.67 in). VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 96 For the version with temperature range up to 150 °C/302 °F, the measure of length increases by 28 mm (1.1 in). For the version with "Second Line of Defense", the measure of length increases by 17 mm (0.67 in). VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 97 F2 Flange DN 80 PN 40 Form C, DIN 2501; with extension For the version with temperature range up to 150 °C/302 °F, the measure of length increases by 28 mm (1.1 in). VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 98 ø 48 mm (1.89") 50 mm 50 mm (1.97") (1.97") Fig. 58: VEGABAR 82, flange connection for the paper industry: CL = absolutely front-flush for headbox, BR = absolutely front-flush for headbox (flange 2-times flattened) VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 99 41 mm (1.63") 65 mm (2.56") Fig. 59: VEGABAR 82, connection acc. to IEC 61518 SJ Oval flange adapter SK Top flange For the version with temperature range up to 150 °C/302 °F, the measure of length increases by 28 mm (1.1 in).
  • Page 100: Industrial Property Rights

    Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec- tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com. VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus- trial. Para mayor información revise la pagina web www.vega.com.
  • Page 101 NAMUR NE 107 53 Parameterization example 37 Peak value indicator 42 Position correction 37 Pressure compensation 19, 20 – Ex d 19 Process pressure measurement 21 Repair 59 Replacement parts – Electronics module for Modbus 16 Reset 43 VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 102 Notes VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 103 Notes VEGABAR 82 • Modbus and Levelmaster protocol...
  • Page 104 Subject to change without prior notice © VEGA Grieshaber KG, Schiltach/Germany 2017 VEGA Grieshaber KG Phone +49 7836 50-0 Am Hohenstein 113...

Table of Contents