Comfort T (Desired Room Temperature In Comfort Mode) 3180; Saving T (Desired Room Temperature In Saving Mode) 3181; Gain - Max. (Room Temp. Limitation, Maximum) 3182; Gain - Min. (Room Temp. Limitation, Minimum) 3183 - Danfoss ECL Comfort 110 Operating Manual

Hide thumbs Also See for ECL Comfort 110:
Table of Contents

Advertisement

Maintenance
Comfort T (desired room temperature in Comfort mode)
Setting the desired room temperature for Comfort mode.
Saving T (desired room temperature in Saving mode)
Setting the desired room temperature for Saving mode.
Gain - max. (room temp. limitation, maximum)
Determines how much the desired flow temperature will be influenced (decreased) if the actual room
temperature gets higher than the desired room temperature (P control).
0.0:
No influence
-2.0:
Minor influence
-5.0:
Medium influence
-9.9:
Maximum influence
Gain - min. (room temp. limitation, minimum)
Determines how much the desired flow temperature will be influenced (increased) if the actual room
temperature gets lower than the desired room temperature (P control).
9.9:
Maximum influence
5.0:
Medium influence
2.0:
Minor influence
0.0:
No influence
Intgr. time (Integration time)
Controls how fast the actual room temperature adapts to the desired room temperature (I control).
The "Intgr. time" function can correct the desired flow temperature with max. 8 degrees.
OFF:
The control function is not influenced by the 'Intgr. time'.
Minor value: The desired room temperature is adapted quickly.
Major value:
The desired room temperature is adapted slowly.
VI.LV.A1.02
Setting range
Setting range
Setting range
Setting range
Setting range
3180
5 . . . 40 °C
3181
5 . . . 40 °C
3182
-9.0 . . . 0.0
3183
0.0 . . . 9.9
3015
OFF / 1 . . . 50 s
© Danfoss | 2016.05 | 13

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ECL Comfort 110 and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents

Save PDF