Maintenance
Room T limit (room temperature limitation)
This section is a general description for Room temperature limitation and is only relevant if
you have installed a room temperature sensor (S2).
The ECL Comfort 110 adjusts the desired flow temperature to compensate for the difference
between the desired and the actual room temperature.
If the room temperature is higher than the desired value, the desired flow temperature can
be reduced.
The 'Gain-max.' (Influence, max. room temp.) determines how much the desired flow
temperature should be reduced.
Use this influence type to avoid a too high room temperature.
If the room temperature is lower than the desired value, the desired flow temperature can
be increased.
The 'Gain-min.´ (Influence, min. room temperature) determines how much the desired flow
temperature should be increased.
Use this influence type to avoid a too low room temperature.
A typical setting will be -4.0 for 'Gain-max.' and 4.0 for 'Gain-min.´
X
=
Room temperature
# 1 #
=
Desired room temperature
# 2 #
=
Negative influence (3182) when actual room temp. gets higher than desired
room temp.
# 3 #
=
Positive influence (3183) when actual room temp. gets lower than desired
room temp.
12 | © Danfoss | 2016.05
3000
VI.LV.A1.02