REM 610
3.1.10.
16
Motor Protection Relay
Operator's Manual
Main Menu
MEASUREMENTS
RECORDED DATA
SETTINGS
CONFIGURATION
INFO
Fig. 3.1.9.-1
Setting the real-time clock
How to switch between front and rear connection
There are two means of serial communication available for the relay: the front
connection for SPA bus communication and the optional rear communication
module for communication via the SPA bus, IEC 60870-5-103 or MODBUS (RTU
or ASCII) protocol.
If the relay is not provided with an optional rear communication module, or if the
module has been disabled, the front connection is always active and switching
between front and rear connection is not allowed.
If the optional rear communication module has been installed and enabled, the
default setting is rear connection. Switch between front and rear connection as
follows:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select CONFIGURATION\COMMUNICATION and
press
. The cursor will be at the setting currently in use (REAR
CONNECTION or FRONT CONNECTION).
3. Press
to enter the setting mode. The second line will start to flash.
4. Use
or
to select the desired setting.
5. Press
to confirm the selection.
6. Press
to return the display to the idle mode.
When the front connection has been selected and there is no communication for
approximately five minutes, the rear connection will automatically be activated. To
keep the front connection continuously active, press
connecting the auxiliary voltage to the relay.
Note!
When rear connection has been selected, the selected rear protocol will
automatically be activated.
Group Menu
CONFIGURATION
FUNCTION TEST/DI
COMMUNICATION
LANGUAGE
MEMORY SETTINGS
FREQUENCY
PASSWORD HMI
TIME
TRIP CIRCUIT SUP
RTD INPUTS
1MRS 752264-MUM
Parameter Menu
CONFIGURATION
Confirm
YY-MM-DD
(00-23)
hh.mm;ss
(00-59)
Cancel
and
simultaneously when