ABB REM 610 Operator's Manual page 34

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

REM 610
34
Motor Protection Relay
Operator's Manual
Table 3.3.2.3-2 Warning codes
Trip-circuit
2
supervision
Power supply
4
module
temperature high
Communication
8
module faulty or
missing
RTD module
16
faulty
Temperature
32
sensor range
error
Sensor circuit
64
open or shorted
(RTD1)
Sensor circuit
128
open or shorted
(RTD2)
Sensor circuit
256
open or shorted
(RTD3)
Sensor circuit
512
open or shorted
(RTD4)
Sensor circuit
1024
open or shorted
(RTD5)
Sensor circuit
2048
open or shorted
(RTD6)
Thermistor circuit
4096
open or shorted
(Thermistor1)
Thermistor circuit
8192
open or shorted
(Thermistor2)
Σ:
16383
1)
Temperature protection stages are out of operation.
• Error in trip circuit
- Check the trip circuit for broken conductors and correct.
- Warning will not be displayed if trip-circuit supervision (TCS)
has been disabled
• Temperature inside relay is too high
- Check that ambient temperature is within service temperature
range
• Communication module faulty or not installed
- Check that plug-in unit is properly attached to relay case
- Check that communication module is installed
- Warning will not be displayed if rear communication module
has been disabled
- In case only this warning is active, it will be displayed in text
format (Comm.card faulty)
Three possible causes:
1) Storing in non-volatile memory has not been successful, which
means that old settings will be taken into use after power up
2) Self calibration has failed
3) Offset voltage out of range
- If warning is not cleared after a power reset, the relay may
require service
• At least one sensor (RTD1...6) is outside measurement range
- Check that sensors are not broken
1)
• Circuit is open or shorted
- Check wiring of sensor
- Check that sensor is not broken
1)
• Circuit is open or shorted
- Check wiring of sensor
- Check that sensor is not broken
1)
• Circuit is open or shorted
- Check wiring of sensor
- Check that sensor is not broken
1)
• Circuit is open or shorted
- Check wiring of sensor
- Check that sensor is not broken
1)
• Circuit is open or shorted
- Check wiring of sensor
- Check that sensor is not broken
1)
• Circuit is open or shorted
- Check wiring of sensor
- Check that sensor is not broken
• Circuit is open or shorted
- Check wiring of thermistor
- Check that thermistor is not broken
• Circuit is open or shorted
- Check wiring of thermistor
- Check that thermistor is not broken
1MRS 752264-MUM