1MRS 752264-MUM
1.
1.1.
1.2.
1.3.
Motor Protection Relay
Operator's Manual

Introduction

About this manual

This manual provides basic information on the protection relay REM 610 Revision
B and presents detailed instructions on how to use the Human-Machine Interface
(HMI) of the relay, also known as the Man-Machine Interface (MMI). In addition to
the instructive part, a short chapter on commissioning and maintenance of the relay
is included.

The use of the relay

REM 610 is a versatile multifunction protection relay mainly designed to protect
motors in a wide range of motor applications.
REM 610 is based on a microprocessor environment. A self-supervision system
continuously monitors the operation of the relay.
The HMI includes a Liquid Crystal Display (LCD) which makes the local use of the
relay safe and easy.
Local control of the relay via serial communication can be carried out with a
computer connected to the front communication port. Remote control can be carried
out via the rear connector connected to the control and monitoring system through
the serial communication bus.

Features

• Three-phase thermal overload protection
• Three-phase motor start-up supervision based on thermal stress calculation with
speed switch blocking ability
• Three-phase overcurrent protection with definite-time characteristic and speed
switch blocking ability
• Three-phase short-circuit protection with instantaneous or definite-time
characteristic
• Three-phase undercurrent (loss of load) protection with definite-time
characteristic
• Non-directional earth-fault protection with definite-time characteristic
• Three-phase unbalance protection based on the negative-phase-sequence current
with inverse definite minimum time characteristic
• Phase reversal protection based on the negative-phase-sequence current
• Cumulative start-up time counter with restart inhibit function
• Circuit-breaker failure protection
• Temperature protection stages with definite-time characteristic
• Emergency start function
• Optional RTD module
• with six measuring inputs
• supports PTC thermistors and various RTD sensors
• three additional galvanically isolated digital inputs