1MRS 755539
3.1.11.
Feeder Protection Relay
Operator's Manual - ANSI Version

How to switch between front and rear connection

There are two means of serial communication available for the relay: the front
connection for SPA bus communication and optional rear communication modules
for communication via the SPA bus, IEC 60870-5-103, MODBUS (RTU or ASCII)
or DNP 3.0 protocol.
If the relay is not provided with an optional rear communication module, or if the
module has been disabled, the front connection is always active and switching
between front and rear connection is not allowed.
If the optional rear communication module has been installed and enabled, the
default setting is rear connection. Switch between front and rear connection as
follows:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select CONFIGURATION\COMMUNICATION and
press
. The cursor will be at the setting currently in use (REAR
CONNECTION or FRONT CONNECTION).
3. Press
to enter the setting mode. The second line will start to flash.
4. Use
or
to select the desired setting.
5. Press
to confirm the selection.
6. Press
to return the display to the idle mode.
When the front connection has been selected and there is no communication for
approximately five minutes, the rear connection will automatically be activated. To
keep the front connection continuously active, press
connecting the auxiliary voltage to the relay.
Note!
When rear connection has been selected, the selected rear protocol will
automatically be activated.
Main Menu
Group Menu
MEASUREMENTS
RECORDED DATA
OPERATION
SETTINGS
CONFIGURATION
CONFIGURATION
FUNCTION TEST/DI
INFO
Fig. 3.1.11.-1
Switching between front and rear connection
Parameter Menu
CONFIGURATION
COMMUNICATION
REAR CONNECTION
REAR PROTOCAL
LANGUAGE
REAR COM. MODULE
MEMORY SETTINGS
SPA SETTINGS
FREQUENCY
IEC103 SETTINGS
PASSWORD HMI
MODBUS SETTINGS
TIME
TRIP CIRCUIT SUP
UNIT ADDRESS
REF 610
and
simultaneously when
CONFIGURATION
REAR CONNECTION
FRONT CONNECTION
COUNTER
LINE-IDLE STATE
CONNECTION TYPE
Confirm
Cancel
17