Smbrrec - ABB Relion 670 series Product Manual

Line distance protection ansi pre-configured
Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

ABB
Line distance protection REL670 ANSI
Pre-configured
Product version: 1.2
Table 46. Autorecloser SMBRREC (79)
Function
Number of autoreclosing shots
Autoreclosing open time:
shot 1 - t1 1Ph
shot 1 - t1 2Ph
shot 1 - t1 3PhHS
shot 1 - t1 3PhDld
shot 2 - t2
shot 3 - t3
shot 4 - t4
shot 5 - t5
Extended autorecloser open time
Autorecloser maximum wait time for sync
Maximum trip pulse duration
Inhibit reset time
Reset time
Minimum time CB must be closed before AR becomes ready for
autoreclosing cycle
Circuit breaker closing pulse length
CB check time before unsuccessful
Wait for master release
Wait time after close command before proceeding to next shot
1MRK 506 317-BUS A
Range or value
Accuracy
1 - 5
-
(0.000-60.000) s
± 0.5% ± 10 ms
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
57