ABB Relion 670 series Product Manual page 53

Line distance protection ansi pre-configured
Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

ABB
Line distance protection REL670 ANSI
Pre-configured
Product version: 1.2
Voltage protection
Table 39. Two step undervoltage protection UV2PTUV (27)
Function
Operate voltage, low and high step
Absolute hysteresis
Internal blocking level, low and high step
Inverse time characteristics for low and
high step, see table
87
Definite time delays
Minimum operate time, inverse
characteristics
Operate time, pickup function
Reset time, pickup function
Critical impulse time
Impulse margin time
Table 40. Two step overvoltage protection OV2PTOV (59)
Function
Operate voltage, low and high step
Absolute hysteresis
Inverse time characteristics for low and
high step, see table
86
Definite time delays
Minimum operate time, Inverse
characteristics
Operate time, pickup function
Reset time, pickup function
Critical impulse time
Impulse margin time
Range or value
(1–100)% of
VBase
(0–100)% of
VBase
(1–100)% of
VBase
-
(0.000-60.000) s
(0.000–60.000) s
25 ms typically at 2 to 0 x V
set
25 ms typically at 0 to 2 x V
set
10 ms typically at 1.2 to 0.8 x V
15 ms typically
Range or value
VBase
(1-200)% of
VBase
(0–100)% of
-
(0.000-60.000) s
(0.000-60.000) s
25 ms typically at 0 to 2 x V
set
25 ms typically at 2 to 0 x V
set
10 ms typically at 0 to 2 x V
set
15 ms typically
1MRK 506 317-BUS A
Accuracy
± 0.5% of V
n
± 0.5% of V
n
± 0.5% of V
n
See table
87
± 0.5% ±10 ms
± 0.5% ± 10 ms
-
-
-
set
-
Accuracy
± 0.5% of V
at V < V
n
± 0.5% of V at V > V
± 0.5% of V
at V < V
n
± 0.5% of V at V > V
See table
86
± 0.5% ± 10 ms
± 0.5% ± 10 ms
-
-
-
-
n
n
n
n
53