Type tests according to standards
Table 19. Electromagnetic compatibility
Test
1 MHz Oscillatory burst disturbance
100 kHz slow damped oscillatory wave immunity
test
Ring wave immunity test, 100 kHz
Surge withstand capability test
Electrostatic discharge
Direct application
Indirect application
Electrostatic discharge
Direct application
Indirect application
Fast transient disturbance
Surge immunity test
Power frequency immunity test
Conducted common mode immunity test
Power frequency magnetic field test
Damped oscillatory magnetic field test
Radiated electromagnetic field disturbance
Radiated electromagnetic field disturbance
Conducted electromagnetic field disturbance
Radiated emission
Conducted emission
Table 20. Insulation
Test
Dielectric test
Impulse voltage test
Insulation resistance
42
Type test values
2.5 kV
2.5 kV
2-4 kV
2.5 kV, oscillatory
4.0 kV, fast transient
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
4 kV
1-2 kV, 1.2/50 ms
high energy
150-300 V
15 Hz-150 kHz
1000 A/m, 3 s
100 A/m, cont.
100 A/m
20 V/m, 80-1000 MHz
1.4-2.7 GHz
35 V/m
26-1000 MHz
10 V, 0.15-80 MHz
30-1000 MHz
0.15-30 MHz
Type test values
2.0 kV AC, 1 min.
5 kV, 1.2/50 ms, 0.5 J
>100 MW at 500 VDC
1MRK 506 317-BUS A
Reference standards
IEC 60255-22-1
IEC 61000-4-18, Class III
IEC 61000-4-12, Class IV
IEEE/ANSI C37.90.1
IEC 60255-22-2, Class IV
IEC 61000-4-2, Class IV
IEEE/ANSI C37.90.1
IEC 60255-22-4, Class A
IEC 60255-22-5
IEC 60255-22-7, Class A
IEC 61000-4-16, Class IV
IEC 61000-4-8, Class V
IEC 61000-4-10, Class V
IEC 60255-22-3
IEEE/ANSI C37.90.2
IEC 60255-22-6
IEC 60255-25
IEC 60255-25
Reference standard
ANSI C37.90
ABB