ABB Relion 670 series Product Manual page 72

Line distance protection ansi pre-configured
Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

Line distance protection REL670 ANSI
Pre-configured
Product version: 1.2
Table 85. RI and RD type inverse time characteristics
Function
RI type inverse characteristic
1
=
×
t
td
0.236
-
0.339
I
EQUATION1656 V1 EN
I = I
/I
measured
set
RD type logarithmic inverse characteristic
æ
ö
I
-
ç
×
÷
=
5.8
1.35
In
t
è
ø
td
EQUATION1657 V1 EN
I = I
/I
measured
set
72
Range or value
td = (0.05-999) in steps of 0.01
td = (0.05-999) in steps of 0.01
1MRK 506 317-BUS A
Accuracy
IEC 60255-3, class 5 +
40 ms
IEC 60255-3, class 5 +
40 ms
ABB