Line distance protection REL670 ANSI
Pre-configured
Product version: 1.2
Station communication
Table 63. IEC 61850-8-1 communication protocol
Function
Protocol
Communication speed for the IEDs
Table 64. LON communication protocol
Function
Protocol
Communication speed
Table 65. SPA communication protocol
Function
Protocol
Communication speed
Slave number
Table 66. IEC60870-5-103 communication protocol
Function
Protocol
Communication speed
Table 67. SLM – LON port
Quantity
Optical connector
Fiber, optical budget
Fiber diameter
*) depending on optical budget calculation
64
Value
IEC 61850-8-1
100BASE-FX
Value
LON
1.25 Mbit/s
Value
SPA
300, 1200, 2400, 4800, 9600, 19200 or 38400 Bd
1 to 899
Value
IEC 60870-5-103
9600, 19200 Bd
Range or value
Glass fiber: type ST
Plastic fiber: type HFBR snap-in
Glass fiber: 11 dB (3000 ft typically *)
Plastic fiber: 7 dB (35 ft 10 m typically *)
Glass fiber: 62.5/125 mm
Plastic fiber: 1 mm
1MRK 506 317-BUS A