ABB Relion 670 series Product Manual page 68

Line distance protection ansi pre-configured
Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

Line distance protection REL670 ANSI
Pre-configured
Product version: 1.2
Basic IED functions
Table 78. Self supervision with internal event list
Data
Recording manner
List size
Table 79. Time synchronization, time tagging
Function
Time tagging resolution, events and sampled measurement values
Time tagging error with synchronization once/min (minute pulse synchronization), events
and sampled measurement values
Time tagging error with SNTP synchronization, sampled measurement values
Table 80. GPS time synchronization module (GTM)
Function
Receiver
Time to reliable time reference with antenna in new
position or after power loss longer than 1 month
Time to reliable time reference after a power loss
longer than 48 hours
Time to reliable time reference after a power loss
shorter than 48 hours
Table 81. GPS – Antenna and cable
Function
Max antenna cable attenuation
Antenna cable impedance
Lightning protection
Antenna cable connector
Accuracy
68
Value
Continuous, event controlled
1000 events, first in-first out
Range or value
Accuracy
±1µs relative UTC
<30 minutes
<15 minutes
<5 minutes
Value
26 db @ 1.6 GHz
50 ohm
Must be provided externally
SMA in receiver end
TNC in antenna end
+/-2μs
1MRK 506 317-BUS A
Value
1 ms
± 1.0 ms typically
± 1.0 ms typically
ABB