ABB
Line distance protection REL670 ANSI
Pre-configured
Product version: 1.2
Table 13. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Function of quantity
Rated voltage
Number of outputs
Impedance open state
Test voltage across open contact, 1 min
Current carrying capacity:
Continuous
1.0s
Making capacity at capacitive load with
the maximum capacitance of 0.2 μF :
0.2s
1.0s
Breaking capacity for DC with L/R ≤ 40ms
Operating time
Static binary output trip
48 - 60 VDC
6
~300 kΩ
No galvanic separation
5A
10A
30A
10A
48V / 1A
60V / 0,75A
<1ms
1MRK 506 317-BUS A
110 - 250 VDC
6
~810 kΩ
No galvanic separation
5A
10A
30A
10A
110V / 0.4A
125V / 0.35A
220V / 0.2A
250V / 0.15A
<1ms
39