Table 54. Disturbance report DRPRDRE
Function
Pre-fault time
Post-fault time
Limit time
Maximum number of recordings
Time tagging resolution
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of phasors in the Trip Value recorder
per recording
Maximum number of indications in a disturbance report
Maximum number of events in the Event recording per
recording
Maximum number of events in the Sequence of events
Maximum total recording time (3.4 s recording time and
maximum number of channels, typical value)
Sampling rate
Recording bandwidth
Table 55. Fault locator LMBRFLO
Function
Reactive and resistive reach
Phase selection
Maximum number of fault
locations
Range or value
(0.05–9.90) s
(0.1–10.0) s
(0.5–10.0) s
100, first in - first out
1 ms
30 + 10 (external + internally
derived)
96
30
96
150
1000, first in - first out
340 seconds (100 recordings) at
50 Hz, 280 seconds (80
recordings) at 60 Hz
1 kHz at 50 Hz
1.2 kHz at 60 Hz
(5-300) Hz
Value or range
(0.001-1500.000) Ω/phase
According to input signals
100
1MRK 506 317-BUS A
Accuracy
-
-
-
-
See table
-
-
-
-
-
-
-
-
-
Accuracy
± 2.0% static accuracy
± 2.0% degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x V
n
Current range: (0.5-30) x I
n
-
-
79
61