ABB Relion 670 series Product Manual page 71

Line distance protection ansi pre-configured
Hide thumbs Also See for Relion 670 series:
Table of Contents

Advertisement

ABB
Line distance protection REL670 ANSI
Pre-configured
Product version: 1.2
Table 84. IEC Inverse time characteristics
Function
Operating characteristic:
æ
ö
A
ç
÷
=
×
t
td
(
)
ç
÷
P
è
-
ø
I
1
EQUATION1653 V1 EN
I = I
/I
measured
set
Time delay to reset, IEC inverse time
IEC Normal Inverse
IEC Very inverse
IEC Inverse
IEC Extremely inverse
IEC Short time inverse
IEC Long time inverse
Programmable characteristic
Operate characteristic:
æ
ö
A
ç
÷
=
+
×
t
B
td
(
)
ç
÷
P
è
-
ø
I
C
EQUATION1654 V1 EN
Reset characteristic:
TR
=
×
t
td
(
)
PR
-
I
CR
EQUATION1655 V1 EN
I = I
/I
measured
set
Range or value
td = (0.05-999) in steps of 0.01
(0.000-60.000) s
A=0.14, P=0.02
A=13.5, P=1.0
A=0.14, P=0.02
A=80.0, P=2.0
A=0.05, P=0.04
A=120, P=1.0
td = (0.05-999) in steps of 0.01
A=(0.005-200.000) in steps of 0.001
B=(0.00-20.00) in steps of 0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of 0.001
TR=(0.005-100.000) in steps of 0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of 0.001
1MRK 506 317-BUS A
Accuracy
-
± 0.5% of set time ± 10 ms
IEC 60255-3, class 5 +
40 ms
IEC 60255, class 5 + 40
ms
71