Eaton EDR-5000 Installation, Operation And Maintenance Manual page 416

Hide thumbs Also See for EDR-5000:
Table of Contents

Advertisement

Global Protection Parameters of the Breaker Wear Module
Parameter
Description
Operations Alarm
Service Alarm, too many Operations
Isum Intr Alarm
Alarm, the Sum (Limit) of interrupting currents has been
exceeded.
Isum Intr ph Alm
Alarm, the per hour Sum (Limit) of interrupting currents
has been exceeded.
Bwear Curve Fc
The Breaker Wear Curve defines the maximum allowed
CLOSE/OPEN cycles depending on the brake currents. If
the breaker maintenance curve is exceeded, an alarm
will be issued. The breaker maintenance curve is to be
taken from the technical data sheet of the breaker
manufactor. By means of the available points this curve
is to be replicated.
WearLevel Alarm
Breaker Wear curve Alarm
Only available if:Bwear Curve Fc = Active
WearLevel Lockout
Breaker Wear Curve Lockout Level
Only available if:Bwear Curve Fc = Active
Current1
Interrupted Current Level #1
Only available if:Bwear Curve Fc = Active
Count1
Open Counts Allowed #1
Only available if:Bwear Curve Fc = Active
Current2
Interrupted Current Level #2
Only available if:Bwear Curve Fc = Active
EDR-5000
Setting range
1 - 100000
0.00 - 2000.00kA
0.00 - 2000.00kA
Inactive,
Active
0.00 - 100.00%
0.00 - 100.00%
0.00 - 2000.00kA
1 - 32000
0.00 - 2000.00kA
www.eaton.com
IM02602007E
Default
Menu path
9999
[Control
/Bkr
/Bwear]
100.00kA
[Control
/Bkr
/Bwear]
100.00kA
[Control
/Bkr
/Bwear]
Inactive
[Control
/Bkr
/Bwear]
80.00%
[Control
/Bkr
/Bwear]
95.00%
[Control
/Bkr
/Bwear]
0.1kA
[Control
/Bkr
/Bwear]
10000
[Control
/Bkr
/Bwear]
1.00kA
[Control
/Bkr
/Bwear]
416