Parameter
Description
Assignment 6
Assignment
Inverting 6
Inverting of the state of the assigned signal.
Assignment 7
Assignment
Inverting 7
Inverting of the state of the assigned signal.
DISARMED Ctrl
Enables and disables the disarming of the relay outputs.
This is the first step of a two step process, to inhibit the
operation or the relay outputs. Please refer to
"DISARMED" for the second step.
Disarm Mode
CAUTION! RELAYS DISARMED in order to safely
perform maintenance while eliminating the risk of taking
an entire process off-line. (Note: Zone Interlocking and
Supervision Contact cannot be disarmed). YOU MUST
ENSURE that the relays are ARMED AGAIN after
maintenance.
t-Timeout DISARM
The relays will be armed again after expiring of this time.
Only available if: Mode = Timeout DISARM
EDR-5000
Setting range
1..n, Assignment
List
Inactive,
Active
1..n, Assignment
List
Inactive,
Active
Inactive,
Active
Permanent,
Timeout
0.00 - 300.00s
www.eaton.com
IM02602007E
Default
Menu path
-.-
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 4]
Inactive
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 4]
-.-
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 4]
Inactive
[Device Para
/Relay Outputs
/RO-4Z X2
/RO 4]
Inactive
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-4Z X2]
Permanent
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-4Z X2]
0.03s
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-4Z X2]