The digital inputs are provided with different switching thresholds (can be parameterized) (two AC and five DC input
ranges). For each group the following switching thresholds can be defined:
24V DC
48V DC / 60V DC
110 V AC/DC
230 V AC/DC
If a voltage >80% of the set switching threshold is applied at the digital input, the state change is recognized (physically
"1"). If the voltage is below 40% of the set switching threshold, the device detects physically "0".
The ground terminal has to be connected to the »-pole« when using DC
supply.
For each digital input group the related voltage input range has to be
parameterized. Wrong switching thresholds can result in
malfunctions/wrong signal transfer times.
Via the »assignment list« the states of the digital inputs are assigned to the
module inputs (e.g. I[1]).