Eaton EDR-5000 Installation, Operation And Maintenance Manual page 31

Hide thumbs Also See for EDR-5000:
Table of Contents

Advertisement

DI-8 X - Power Supply and Digital Inputs
This assembly group comprises:
A wide-range power supply unit;
Two non-grouped digital inputs; and
Six (6) digital inputs, grouped.
Auxiliary Voltage Supply
The auxiliary voltage inputs (wide-range power supply unit) are non-polarized. The device can be powered with
an AC or DC control voltage.
Digital Inputs
The digital inputs are provided with different switching thresholds (that are configurable) (two AC and five DC input
ranges). The following switching levels can be defined:
24 Vdc;
48 Vdc
60 Vdc;
110/120 Vac/dc; and
230/240 Vac/dc.
If a voltage >80% of the set switching threshold is applied at the digital input, the state change is recognized (logically
"1"). If the voltage is below 40% of the set switching threshold, the device detects logically "0".
Make sure that the tightening torque is 5-7 In-lb [0.56-0.79 Nm].
For each digital input group, the related voltage input range has to be
configured. Wrong switching thresholds can result in malfunctions/wrong signal
transfer times.
When using DC supply, the negative potential has to be connected to the
common terminal (COM1, COM2, COM3 - please see the terminal marking).
EDR-5000
www.eaton.com
IM02602007E
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents