Belt conveyor scale integrator

Advertisement

No.
Parameter
2A
Testing ROM
2B
Testing RAM
2C
Testing E2PROM
3
Dig input test
4
Dig output test
Output #___ ___
5A
Current output #1
should be ____
5B
Current output #2
should be ____
5C
Current output #3
should be ____
Thermo Fisher Scientific
Selection
PASSED, FAILED
PASSED, FAILED
PASSED, FAILED
Slot #0 : ---0001-
Slot #1: 00000000
Slot #2: 00000000
Slot #3: 00000000
Slot #4: 00000000
(1-13) (OFF, ON)
4.00 mA
(4-20) (0-20) (20-0)
(20-4)
4.00 mA
(4-20) (0-20) (20-0)
(20-4)
4.00 mA
(4-20) (0-20) (20-0)
(20-4)
Description
The message Test PASSED is
displayed if the test runs
correctly. If something wrong is
detected, the message Test
FAILED is displayed, and the soft
key CONTINUE is shown. You
must press the key to go on to
the next test. (Password:
Service.)
Shows the status of each digital
input.
Slots are numbered 1 to 4. Slot
0 is the motherboard. Inputs are
shown from left to right.
(Password: Service.)
Output range based on number
of DIO 8in/8out boards installed.
Shows the status of each digital
output and allows the operator to
force the output for testing
purposes. The output, when
forced, stays on until the CLEAR
soft key is pressed or the Run
Menu is entered.
If an output is forced and the
scroll key is used for reaching
some other menu, the output
stays in the forced status until
RUN is pressed. This allows you
to check inputs while outputs are
still in the forced status.
NOTE. Forcing the digital outputs
may cause machinery to start.
This scroll is only available when
a current output board is
installed.
To force the output, use the
numeric keys to enter the desired
number of mill amperes. Press
ENTER to confirm. Press CLEAR
to free the mA channel.
(Password: Service.)
"
"
Micro-Tech 9101/9201 Reference Manual, Rev J