Open System Wiring Specifications And Recommended Vendors - Carrier 23XRV Installation Instructions Manual

High-efficiency variable speed screw chiller with greenspeed intelligence 50/60 hz hfc-134a
Hide thumbs Also See for 23XRV:
Table of Contents

Advertisement

Table 25 — Open System Wiring Specifications and Recommended Vendors
WIRING SPECIFICATIONS
WIRE TYPE
22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
MS/TP
specifications.
NETWORK
24 AWG, single twisted shielded pair, low capacitance, CL2P,
(RS-485)
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.
RNET
4 conductor, unshielded, CMP, 18 AWG, plenum rated.
LEGEND
AWG
— American Wire Gage
CL2P
— Class 2 Plenum Cable
CMP
— Communications Plenum Rated
FEP
— Fluorinated Ethylene Polymer
TC
— Tinned Copper
DESCRIPTION
72
RECOMMENDED VENDORS AND PART NUMBERS
CONNECT AIR
INTERNATIONAL BELDEN RMCORP
W221P-22227
W241P-2000F
82841
W184C-2099BLB
6302UE
CONTRACTORS
WIRE AND
CABLE
25160PV
CLP0520LC
25120-OR
21450
CLP0442