Bt485 Terminator Installation; Ms/Tp Wiring Recommendations - Carrier 23XRV Installation Instructions Manual

High-efficiency variable speed screw chiller with greenspeed intelligence 50/60 hz hfc-134a
Hide thumbs Also See for 23XRV:
Table of Contents

Advertisement

SPECIFICATION
CABLE
CONDUCTOR
INSULATION
COLOR CODE
TWIST LAY
SHIELDING
JACKET
DC RESISTANCE
CAPACITANCE
CHARACTERISTIC IMPEDANCE
WEIGHT
UL TEMPERATURE RATING
VOLTAGE
LISTING
LEGEND
AWG
— American Wire Gage
CL2P
— Class 2 Plenum Cable
DC
— Direct Current
FEP
— Fluorinated Ethylene Polymer
NEC
— National Electrical Code
O.D.
— Outside Diameter
TC
— Tinned Copper
UL
— Underwriters Laboratories
Fig. 77 — BT485 Terminator Installation
Table 24 — MS/TP Wiring Recommendations
Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable
22 or 24 AWG stranded copper (tin plated)
Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.
Black/White
2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal
Aluminum/Mylar shield with 24 AWG TC drain wire
SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.
15.2 Ohms/1000 feet (50 Ohms/km) nominal
12.5 pF/ft (41 pF/meter) nominal conductor to conductor
100 Ohms nominal
12 lb/1000 feet (17.9 kg/km)
SmokeGard 167°F (75°C)
Halar -40 to 302°F (-40 to 150°C)
300 Vac, power limited
UL: NEC CL2P, or better
71
RECOMMENDATION