Carrier 19XL Installation Instructions Manual

Hermetic centrifugal liquid chillers

Advertisement

For Units Produced After 11/1/92 (Linear Float Design)
Centrifugal liquid chillers are designed to provide safe
and reliable service when operated within design speci-
fications. When operating this equipment, use good judg-
ment and safety precautions to avoid damage to equip-
ment and property or injury to personnel.
Be sure you understand and follow the procedures and
safety precautions contained in the chiller instructions,
as well as those listed in this guide.
DO NOT VENT refrigerant relief devices within a building. Outlet from
rupture disc or relief valve must be vented outdoors in accordance with
the latest edition of ANSI/ASHRAE 15 (American National Standards
Institute/American Society of Heating, Refrigeration, and Air Condi-
tioning Engineers). The accumulation of refrigerant in an enclosed space
can displace oxygen and cause asphyxiation.
PROVIDE
adequate
ventilation
ASHRAE 15, especially for enclosed and low overhead spaces. Inha-
lation of high concentrations of vapor is harmful and may cause heart
irregularities, unconsciousness, or death. Intentional misuse can be fa-
tal. Vapor is heavier than air and reduces the amount of oxygen avail-
able for breathing. Product causes eye and skin irritation. Decompo-
sition products are hazardous.
DO NOT USE OXYGEN to purge lines or to pressurize a chiller for
any purpose. Oxygen gas reacts violently with oil, grease, and other
common substances.
DO NOT USE air to leak test. Use only refrigerant or dry nitrogen.
NEVER EXCEED specified test pressures. VERIFY the allowable test
pressure by checking the instruction literature and the design pressures
on the equipment nameplate.
DO NOT VALVE OFF any safety device.
BE SURE that all pressure relief devices are properly installed and func-
tioning before operating any chiller.
DO NOT WELD OR FLAMECUT any refrigerant line or vessel until
all refrigerant (liquid and vapor) has been removed from chiller. Traces
of vapor should be displaced with dry air or nitrogen and the work area
should be well ventilated. Refrigerant in contact with an open flame
produces toxic gases.
DO NOT USE eyebolts or eyebolt holes to rig chiller sections or the
entire assembly.
DO NOT work on high-voltage equipment unless you are a qualified
electrician.
DO NOT WORK ON electrical components, including control
panels, switches, starters, or oil heater until you are sure ALL POWER
IS OFF and no residual voltage can leak from capacitors or solid-state
components.
LOCK OPEN AND TAG electrical circuits during servicing. IF WORK
IS INTERRUPTED, confirm that all circuits are deenergized before
resuming work.
AVOID SPILLING liquid refrigerant on skin or getting it into the eyes.
USE SAFETY GOGGLES. Wash any spills from the skin with soap
and water. If liquid refrigerant enters the eyes, IMMEDIATELY FLUSH
EYES with water and consult a physician.
NEVER APPLY an open flame or live steam to a refrigerant
cylinder. Dangerous over pressure can result. When it is necessary to
heat refrigerant, use only warm (110 F [43 C]) water.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2
PC 211
Catalog No. 531-972
Tab
5a
Hermetic Centrifugal Liquid Chillers

Installation Instructions

SAFETY CONSIDERATIONS

in
accordance
with ANSI/
Printed in U.S.A.
with HCFC-22 and HFC-134a
DO
NOT
REUSE
disposable
attempt to refill them. It is DANGEROUS AND ILLEGAL. When cyl-
inder is emptied, evacuate remaining gas pressure, loosen the collar,
and unscrew and discard the valve stem. DO NOT INCINERATE.
CHECK THE REFRIGERANT TYPE before adding refrigerant to the
chiller. The introduction of the wrong refrigerant can cause
chiller damage or malfunction.
Operation of this equipment with refrigerants other than those cited
herein should comply with ANSI/ASHRAE-15 (latest edition). Con-
tact Carrier for further information on use of this chiller with other
refrigerants.
DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while
chiller is under pressure or while chiller is running. Be sure pressure is
at 0 psig (0 kPa) before breaking any refrigerant connection.
CAREFULLY INSPECT all relief valves, rupture discs, and other
relief devices AT LEAST ONCE A YEAR. If chiller operates in a cor-
rosive atmosphere, inspect the devices at more frequent intervals.
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief valve
when corrosion or build-up of foreign material (rust, dirt, scale, etc.) is
found within the valve body or mechanism. Replace the valve.
DO NOT install relief devices in series or backwards.
USE CARE when working near or in line with a compressed spring.
Sudden release of the spring can cause it and objects in its path to act
as projectiles.
DO NOT STEP on refrigerant lines. Broken lines can whip about and
release refrigerant, causing personal injury.
DO NOT climb over a chiller. Use platform, catwalk, or staging. Fol-
low safe practices when using ladders.
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move
inspection covers or other heavy components. Even if components are
light, use mechanical equipment when there is a risk of slipping or
losing your balance.
BE AWARE that certain automatic start arrangements CAN ENGAGE
THE STARTER, TOWER FAN, OR PUMPS. Open the disconnect ahead
of the starter, tower fan, and pumps. Shut off the chiller or pump before
servicing equipment.
USE only repaired or replacement parts that meet the code require-
ments of the original equipment.
DO NOT VENT OR DRAIN waterboxes containing industrial brines,
liquid, gases, or semisolids without the permission of your process con-
trol group.
DO NOT LOOSEN waterbox cover bolts until the waterbox has been
completely drained.
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or other
items have been removed before rotating any shafts.
DO NOT LOOSEN a packing gland nut before checking that the nut
has a positive thread engagement.
PERIODICALLY INSPECT all valves, fittings, and piping for corro-
sion, rust, leaks, or damage.
PROVIDE A DRAIN connection in the vent line near each pressure
relief device to prevent a build-up of condensate or rain water.
Form 19XL-4SI
Pg 1
19XL
50/60 Hz
(nonreturnable)
cylinders
or
6-96
Replaces: 19XL-3SI

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 19XL

  • Page 1: Safety Considerations

    Operation of this equipment with refrigerants other than those cited herein should comply with ANSI/ASHRAE-15 (latest edition). Con- tact Carrier for further information on use of this chiller with other refrigerants. DO NOT VENT refrigerant relief devices within a building. Outlet from DO NOT ATTEMPT TO REMOVE fittings, covers, etc., while...
  • Page 2: Table Of Contents

    Job Data ........2 standard 19XL chiller is shipped with a full refrig- Equipment Required .
  • Page 3 19 — Linear Float Valve Chamber 20 — Cooler Refrigerant Isolation Valve 21 — Condenser Auto Reset Relief Valves 22 — Condenser Water Temperature Sensors 23 — Chilled Water Temperature Sensors Fig. 2 — Typical 19XL Installation (300 to 600 Tons [1055 to 2110 kW])
  • Page 4: Rigging The Chiller

    RIG CHILLER COMPONENTS — Refer to instructions be- Rigging the Chiller — The 19XL chiller can be rigged low, Fig. 5-9, and Carrier Certified Prints for chiller com- as an entire assembly. It also has flanged connections that ponent disassembly.
  • Page 5 Engineers) 15, latest edition, National Fire Protection Association (NFPA) ft-in. 70, and local safety code. 2. Allow at least 3 ft (915 mm) overhead clearance for service rigging. 1219 3. Certified drawings available upon request. Fig. 4 — 19XL Dimensions...
  • Page 6 *This data is based on the standard waterbox weight at 150 psi (1034 kPa) pressure. †Rigging weights are for standard tubes of standard wall thickness. For special tubes, refer to the 19XL Computer Selection Program. **Refrigerant charge listed is the same for both HCFC-22 and HFC-134a.
  • Page 7 Table 5 — 19XL Waterbox Cover Weights* ENGLISH (lb) FRAME 4, FRAME 4, FRAME 5, FRAME 5, HEAT WATERBOX STD NOZZLES FLANGED STD NOZZLES FLANGED EXCHANGER DESCRIPTION 150 psig 300 psig 150 psig 300 psig 150 psig 300 psig 150 psig...
  • Page 8 LEGEND 1 — Cooler Liquid Feed Line 2 — Heat Exchanger Separation Points Fig. 5 — 19XL Condenser Drain LEGEND 1 — Condenser Discharge Line 2 — Flared Fitting on Isolation Valve Fig. 6 — 19XL Motor End View...
  • Page 9 10 — Guide Vane Actuator Cable 5 — Oil Sump Sensor Cable 11 — Suction Elbow 6 — Discharge Sensor Cable Fig. 7 — 19XL Chiller Top View LEGEND LEGEND 1 — Motor Refrigerant Return Line 1 — Flared Fittings for Oil Reclaim Lines Fig.
  • Page 10: Install Chiller Supports

    (supplied by Carrier for field installa- tion) and leveling pads. Refer to Fig. 10 and 12. NOTE: The motor end of the 19XL compressor is heavy and the compressor will tip to the motor end unless the motor Level chiller by using jacking screws in isolation sole- end is supported.
  • Page 11: Install Spring Isolation

    4 soleplates, 16 jacking screws and leveling pads. Re- quires accessory spring isolators package. Fig. 12 — Accessory Isolation NOTE: The accessory spring isolators are supplied by Carrier for in- stallation in the field. Fig. 13 — 19XL Accessory Spring Isolation (Shown with Accessory Soleplates) NOTE: A field supplied and installed, low-profile isolation is sug-...
  • Page 12: Connect Piping

    2. Provide openings in water piping for required pressure Connect Piping gages and thermometers. For thorough mixing and tem- INSTALL WATER PIPING TO HEAT EXCHANGERS — perature stabilization, wells in the leaving water pipe should Install piping using job data, piping drawings, and proce- extend inside pipe at least 2 in.
  • Page 13 DRIVE END COMPRESSOR END NOZZLE-IN-HEAD WATERBOXES DRIVE END COMPRESSOR END FRONT VIEW DRIVE END COMPRESSOR END MARINE WATERBOXES DRIVE END COMPRESSOR END FRONT VIEW NOZZLE ARRANGEMENT CODES COOLER WATERBOXES CONDENSER WATERBOXES Arrangement Arrangement Pass Code Code WATERBOX NOZZLE SIZES NOMINAL PIPE SIZE (in.) ACTUAL PIPE ID (in.) ACTUAL PIPE OD (in.) PASS...
  • Page 14 DIMENSIONS ENGLISH (ft-in.) TANK SIZE 0428 10- 5 9-10 ⁄ ⁄ ⁄ 4-11 ⁄ 3- 8 ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ ⁄ 0452 14-11 ⁄ 14- 4 ⁄ ⁄ ⁄ ⁄ ⁄ 7- 2 ⁄ 3-11 ⁄ ⁄ ⁄ ⁄...
  • Page 15 STORAGE TANK: RATED DRY WEIGHT AND REFRIGERANT CAPACITY ENGLISH (lb) MAXIMUM REFRIGERANT CAPACITY (lb) TANK TANK OD WEIGHT* ASHRAE/ANSI 15 UL 1963 SIZE (in.) (lb) (HCFC-22) (HFC-134a) (HCFC-22) (HFC-134a) 0428 24.00 2380 1842 1860 1704 1716 0452 27.25 3460 3460 3563 3264 3286...
  • Page 16 Fig. 18 — Optional Pumpout System Piping Schematic with Storage Tank Fig. 19 — Typical Optional Pumpout System Piping Schematic without Storage Tank...
  • Page 17: Install Vent Piping To

    INSTALL VENT PIPING TO RELIEF DEVICES — The low-voltage wiring (50 v maximum). 19XL chiller is factory equipped with relief devices on the cooler and condenser shells. Refer to Fig. 21 and Table 6 for Wiring diagrams in this publication (Fig. 22-29) are for size and location of relief devices.
  • Page 18 Fig. 22 — Carrier Comfort Network Communication Bus Wiring LEGEND *Field supplied terminal strip must be located in control panel. Factory Wiring †Switches S1 and S2 are factory set on PSIO modules and should not be altered. Field Wiring Fig. 23 — COMM1 CCN Communication Wiring For Multiple Chillers (Typical)
  • Page 19: Connect Control Outputs

    3 — Control Cabinet 2. All wiring must comply with applicable codes. 4 — Power Panel 3. Refer to Carrier System Design Manual for details regarding piping techniques. 5 — Vents 4. Wiring not shown for optional devices such as: 6 —...
  • Page 20: Item

    3 — Compressor Motor Terminal Box 2. All wiring must comply with applicable codes. 4 — Chiller Power Panel 3. Refer to Carrier System Design Manual for details regarding piping techniques. 5 — Control Cabinet 4. Wiring not shown for optional devices such as: 6 —...
  • Page 21 10 amps at 115 vac up to 3 amps at 600 vac. Control wiring required *Indicates chilled water pump control contacts or run status contacts. for Carrier to start pumps and tower fan motors must be provided to assure chiller †Indicates condenser water pump control contacts.
  • Page 22: Item

    (lead 1.5 WARNING — Do not use aluminum conductors. connectors not supplied by Carrier). Either 3 or 6 leads must be run between com- pressor motor and starter, depending on type of motor starter employed. If only 3 1.6 Installer is responsible for any damage caused by improper wiring between starter...
  • Page 23: Carrier Comfort Network Interface

    (one point only). Oil Pump Terminal Power Panel Component Terminal To connect the 19XL chiller to the network, proceed as follows (Fig. 23): Fig. 28 — Oil Pump Wiring 1. Cut power to the PIC control panel.
  • Page 24: Install Field Insulation

    • compressor motor sulated to prevent water condensation (Fig. 30, darker • cooler shell shading). • cooler tube sheets • suction piping Fig. 30 — 19XL Insulation Area...
  • Page 26 Copyright 1996 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 2 PC 211 Catalog No. 531-972 Printed in U.S.A. Form 19XL-4SI Pg 26 6-96 Replaces: 19XL-3SI...
  • Page 27: Installation Start-Up Request Checklist

    Other 8. The motor starter has not been supplied by Carrier. It has been installed according to the manufacturer’s instructions. 9. The motor starter has not been supplied by Carrier and it has been checked for proper operation. COMMENTS: CL-1...
  • Page 28 Concerns about the installation/request for additional assistance: I am aware that the start-up time for a Carrier chiller can take between 2 and 6 days depending on the model of the chiller and the options and accessories used with it.

Table of Contents