INSTALL ACCESSORY ISOLATION (if required) —
Uneven floors or other considerations may dictate the use of
accessory soleplates (supplied by Carrier for field installation)
and leveling pads. Refer to Fig. 48.
Level machine by using jacking screws in isolation sole-
plates. Use a level at least 24-in. (610 mm) long.
IMPORTANT: Chiller support plates must be level
within
1
/
in. from one end to the other end of the heat
2
exchangers for effective oil reclaim system operation.
For adequate and long lasting machine support, proper
grout selection and placement is essential. Carrier recommends
that only pre-mixed, epoxy type, non-shrinking grout be used
for machine installation. Follow manufacturer's instructions in
applying grout.
1. Check machine location prints for required grout
thickness.
2. Carefully wax jacking screws for easy removal from
grout.
3. Grout must extend above the base of the soleplate and
there must be no voids in grout beneath the plates.
4. Allow grout to set and harden, per manufacturer's
instructions, before starting machine.
5. Remove jacking screws from leveling pads after grout
has hardened.
14'-9"
[4496mm]
14'-0 3/4"
[4286mm]
REAR
SUPPORT PLATE
C L
COOLER & COMPRESSOR
C L
X*
CONDENSER
FRONT
0'-3"
[76mm]
TYPICAL
ACCESSORY SOLEPLATE
Fig. 45 — 23XRV Frame Size B Machine Footprint
a23-46
0'-9"
[229mm]
TYPICAL
.
ACCESSORY SOLEPLATE DETAIL
a19-1109
LEGEND
HRS — Hot Rolled Steel
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Accessory (Carrier supplied, field installed) soleplate pack-
age includes 4 soleplates, 16 jacking screws and leveling
pads.
3. Jacking screws to be removed after grout has set.
4. Thickness of grout will vary, depending on the amount nec-
essary to level chiller. Use only pre-mixed non-shrinking
grout,
Ceilcote 748 OR Chemrex Embeco 636 Plus Grout 0-1½
(38.1) to 0-2¼ (57) thick.
Fig. 48 — Accessory Isolation
41
OUTSIDE EDGE O
COOLER TUBESH
(TYPICAL BOTH E
OUTSIDE EDGE OF
CONDENSER TUBE
(TYPICAL BOTH EN
1'-3 1/4"
[387mm]
TYPICAL
Y
Y*
DISCHARGE END
a23-1684
/LEG
VIEW X-X
a19-1110
0'-1 1/2"
[38mm]
TYPICAL
3'-3 1/4"
[997mm]
1'-3 7/8"
[403mm]

Advertisement

Table of Contents
loading

Table of Contents