INSTALL ACCESSORY ISOLATION (IF REQUIRED)

Uneven floors or other considerations may dictate the use of ac-
cessory soleplates (supplied by Carrier for field installation) and
leveling pads. Refer to Fig. 44.
Level machine by using jacking screws in isolation soleplates. Use
a level at least 24 in. (610 mm) long.
IMPORTANT: Chiller support plates must be level within
1/2 in. from one end to the other end of the heat exchang-
ers for effective oil reclaim system operation.
For adequate and long lasting machine support, proper grout se-
lection and placement is essential. Carrier recommends that only
pre-mixed, epoxy type, non-shrinking grout be used for machine
installation. Follow manufacturer's instructions in applying grout.
1.
Check machine location prints for required grout thickness.
2.
Carefully wax jacking screws for easy removal from grout.
3.
Grout must extend above the base of the soleplate and there
must be no voids in grout beneath the plates.
4.
Allow grout to set and harden, per manufacturer's instruc-
tions, before starting machine.
5.
Remove jacking screws from leveling pads after grout has
hardened.
14'-9"
[4496mm]
14'-0 3/4"
[4286mm]
REAR
SUPPORT PLATE
C L
EVAPORATOR & COMPRESSOR
C L
X*
CONDENSER
FRONT
0'-3"
[76mm]
TYPICAL
ACCESSORY SOLEPLATE
Fig. 42 — 23XRV Frame Size B Machine Footprint
a23-46
0'-9"
[229mm]
TYPICAL
Y
DISCHARGE END
ACCESSORY SOLEPLATE DETAIL
LEGEND
HRS — Hot Rolled Steel
NOTES:
1. Dimensions in ( ) are in millimeters.
2. Accessory (Carrier supplied, field installed) soleplate package
includes 4 soleplates, 16 jacking screws and leveling pads.
3. Jacking screws to be removed after grout has set.
4. Thickness of grout will vary, depending on the amount neces-
sary to level chiller. Use only pre-mixed non-shrinking grout,
Ceilcote 748 OR Chemrex Embeco 636 Plus Grout 0-1-1/2
(38.1) to 0-2-1/4 (57) thick.
Fig. 44 — Accessory Isolation
37
OUTSIDE EDGE OF
EVAPORATOR TUBESHEET.
(TYPICAL BOTH ENDS)
OUTSIDE EDGE OF
CONDENSER TUBESHEET.
(TYPICAL BOTH ENDS)
0'-1 1/2"
[38mm]
TYPICAL
3'-3 1/4"
[997mm]
1'-3 1/4"
[387mm]
TYPICAL
1'-3 7/8"
[403mm]
Y*
a23-1684
/LEG
VIEW X-X
a19-1110