Modbus Map, continued
Modbus
Modbus
Coil Number
Register Number
—
419
—
420
—
421
—
422
—
423
—
424
—
425
—
426
—
427
—
428
—
429
—
430
—
431
—
432
—
433
—
434
—
435
—
436
—
437
—
438
—
439
—
440
—
441
R/W
DCI Descriptor
R/W
Reserved
R/W
Reserved
R/W
Reserved
R/W
DCI_CURRENT_UNBALANCE_TRIP_LEVEL
R/W
DCI_CURRENT_UNBALANCE_TRIP_DELAY
R/W
DCI_LOAD_DISCONNECT_TRIP_LEVEL
R/W
DCI_LOAD_DISCONNECT_TRIP_DELAY_SECONDS
R/W
DCI_LOAD_DISCONNECT_SOURCE
R/W
DCI_PHASE_LOSS_TRIP_LEVEL
R/W
DCI_PHASE_LOSS_TRIP_DELAY
R/W
DCI_UNDER_VOLTAGE_PERCENT
R/W
DCI_UNDER_VOLTAGE_TRIP_DELAY_SECONDS
R/W
DCI_OVER_VOLTAGE_PERCENT
R/W
DCI_OVER_VOLTAGE_TRIP_DELAY_SECONDS
R/W
DCI_VOLTAGE_UNBALANCE_PERCENT
R/W
DCI_VOLTAGE_UNBALANCE_TRIP_DELAY
R/W
DCI_PHASE_SEQUENCE
R/W
DCI_FAULT_RELAY_CONFIGURATION
R/W
DCI_AUX_RELAY_CONFIGURATION
R/W
DCI_UI_EDIT_LOCK
R/W
DCI_USER_DISPLAY_CONFIG
R/W
DCI_MODBUS_ADDRESS
R/W
DCI_MODBUS_BAUD_RATE
S611 Soft Starter MN03902011E—May 2012 www.eaton.com
www.comoso.com
Notes
—
—
—
%, 0–100 (2)
Seconds 1–20 (5)
%rated, 1–50 (6)
Seconds, 1–60 (5)
0 = Under power
1 = Under current
%, 0–100 (40)
Seconds 1–20 (2)
%, 1–99 (90)
Seconds 1–60 (10)
%, 101–120 (110)
Seconds 1–60 (10)
%, 1–20 (6)
Seconds 1–60 (10)
1 = ABC
2 = ACB
0 = Faulted
1 = Not faulted
0 = Faulted
1 = Not faulted
2 = Bypass
3 = Not in bypass
4 = Motor energized
5 = Not motor energized
0 = Unlocked
1 = Locked
0 = Thermal capacity
1 = Power factor
2 = Line frequency
3 = Reserved
4 = Voltage imbal %
5 = Current imbal %
6 = Run time
7 = Average pole temp
8 = Pole A temp
9 = Pole B temp
10 = Pole C temp
1–247 (1)
0 = 1200
1 = 2400
2 = 4800
3 = 9600
4 = 19200 (default)
5 = 38400
6 = 57600
7 = 115200
8 = Reserved
Changes take place on next power cycle
71