Advanced Operation Mode, continued
Code
Parameter
P.09
Relay 2 (96, 97, 98)
P.10
Relay 1 (13, 14)
P.11
Start Control (Level/Edge)
P.12
Jam Trip Delay
P.13
Ground Fault Trip Enable
P.15
Ground Fault Trip Delay
P.16
Ground Fault Start Delay
P.17
Current Imbalance Trip Delay
P.18
Current Phase Loss Trip Delay
P.19
Under Load Trip Delay
P.20
Under Load Source
P.21
Under Voltage Trip Delay
P.22
Over voltage Trip Delay
P.23
Voltage Imbalance Trip Delay
P.24
UI Comm Loss Fault Enable
P.25
Shorted SCR Fault Enable
P.26
SCR Not Firing Fault Enable
P.27
Over Temperature Fault Enable
P.28
Overload on Start Enable
P.29
Command Register
S611 Soft Starter MN03902011E—May 2012 www.eaton.com
42
Minimum
Maximum
0
1
0
5
0
1
1
20
0
1
1
20
0
20
1
20
1
20
1
60
0
1
1
20
1
20
1
20
0
1
0
1
0
1
0
1
0
1
0
3
www.comoso.com
Default
Notes
0
0 = Faulted
1 = Not faulted
2
0 = Faulted
1 = Not faulted
2 = Run (in bypass)
3 = Not in bypass
4 = Motor energized
5 = Motor not energized
1
1 = Level
0 = Edge
2
0
0 = Disable
1 = Enable
2
Value in seconds
1
Value in seconds
5
Value in seconds
2
Value in seconds
5
Value in seconds
0
0 = Trip on low kW%
1 = Trip on under current %
10
Value in seconds
10
Value in seconds
10
Value in seconds
1
0 = No fault on UI disconnect or comm loss
1 = Faulted
1
0 = Disable
1 = Enable
1
0 = Disable
1 = Enable
1
0 = Disable
1 = Enable
1
0 = Disable
1 = Enable
0
0 = No action
1 = Clear motor run hours
2 = Clear motor start count
3 = Clear fault queue