Modbus Map, continued
Modbus
Modbus
Coil Number
Register Number
402
403
404
405
406
407
408
409
410
411
412
413
414
6609
6610
6611
6612
6613
6614
6615
6616
6617
6618
6619
6620
6621
6622
6623
6624
415
416
417
418
S611 Soft Starter MN03902011E—May 2012 www.eaton.com
70
R/W
DCI Descriptor
R/W
DCI_COMMAND_REGISTER
R/W
DCI_CONFIGURATION_RESET
R/W
DCI_OVERLOAD_FLA
R/W
DCI_MOTOR_RATED_VOLTAGE
R/W
DCI_START_METHOD
R/W
DCI_START_TIME
R/W
DCI_INITIAL_TORQUE
R/W
DCI_STOP_TIME
R/W
Reserved
R/W
DCI_KICK_START_TIME
R/W
DCI_KICK_START_TORQUE
R/W
DCI_RESET_MODE
R/W
DCI_ENABLE_DISABLE_TRIP
Overload
Jam
Stall
Current Imbalance
Load Disconnect
Phase Loss
Under Voltage
Over Voltage
Voltage Unbalance
Phase Reversal
Ground Fault
Overload On Start
Shorted SCR
SCR Not Firing
Over Temp
R/W
DCI_OVERLOAD_TRIP_CLASS
R/W
DCI_JAM_TRIP_LEVEL
R/W
DCI_JAM_TRIP_DELAY_SECONDS
R/W
DCI_STALL_TRIP_LEVEL
www.comoso.com
Notes
1 = Clear motor run hours
2 = Clear motor start count
3 = Clear fault queue
1 = Soft reset
2 = Factory defaults
Amps * 10
Volts, 115–600, (Default = 480)
0 = Vramp
1 = Limit
2 = Pump
Seconds*10, 0.5–180 (20)
%, 0–100 (45)
Seconds*10, 0–120 (0, no pump stop option, 50
with pump stop enabled)
Seconds*10, 0–2 (0)
%, 0–100 (0)
0 = Manual
1 = Auto
5–30, (20)
%FLA, 150–400 (300)
Seconds 1–20 (2)
%FLA, 150–300 (200)