Modbus Map, continued
Modbus
Modbus
Coil Number
Register Number
—
402
—
403
—
404
—
405
—
406
—
407
—
408
—
409
—
410
—
411
—
412
—
413
—
414
6609
—
6610
—
6611
—
6612
—
6613
—
6614
—
6615
—
6616
—
6617
—
6618
—
6619
—
6620
—
6621
—
6622
—
6623
—
6624
—
—
415
—
416
—
417
—
418
S611 Soft Starter MN03902011E—May 2012 www.eaton.com
70
R/W
DCI Descriptor
R/W
DCI_COMMAND_REGISTER
R/W
DCI_CONFIGURATION_RESET
R/W
DCI_OVERLOAD_FLA
R/W
DCI_MOTOR_RATED_VOLTAGE
R/W
DCI_START_METHOD
R/W
DCI_START_TIME
R/W
DCI_INITIAL_TORQUE
R/W
DCI_STOP_TIME
R/W
Reserved
R/W
DCI_KICK_START_TIME
R/W
DCI_KICK_START_TORQUE
R/W
DCI_RESET_MODE
R/W
DCI_ENABLE_DISABLE_TRIP
—
Overload
—
Jam
—
Stall
—
Current Imbalance
—
Load Disconnect
—
Phase Loss
—
Under Voltage
—
Over Voltage
—
Voltage Unbalance
—
Phase Reversal
—
Ground Fault
—
Overload On Start
—
Shorted SCR
—
SCR Not Firing
—
Over Temp
—
—
R/W
DCI_OVERLOAD_TRIP_CLASS
R/W
DCI_JAM_TRIP_LEVEL
R/W
DCI_JAM_TRIP_DELAY_SECONDS
R/W
DCI_STALL_TRIP_LEVEL
www.comoso.com
Notes
1 = Clear motor run hours
2 = Clear motor start count
3 = Clear fault queue
1 = Soft reset
2 = Factory defaults
Amps * 10
Volts, 115–600, (Default = 480)
0 = Vramp
1 = Limit
2 = Pump
Seconds*10, 0.5–180 (20)
%, 0–100 (45)
Seconds*10, 0–120 (0, no pump stop option, 50
with pump stop enabled)
—
Seconds*10, 0–2 (0)
%, 0–100 (0)
0 = Manual
1 = Auto
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
5–30, (20)
%FLA, 150–400 (300)
Seconds 1–20 (2)
%FLA, 150–300 (200)