Installation Leaflet IL04209006E
PROFIBUS Module for use with
Motor Insight, C440 and S611
Installation
The PROFIBUS module is designed to be used in
industrial applications and installed in accordance
with this document.
Mount the Module
To mount the
Insight
ceedure must be preformed.
Place the tabs opposite the PROFIBUS con-
nector into the lower slots provided on the
Motor Insights right side.
Pivot the module on the lower tabs toward
the Motor Insight.
Gently press the module and Motor Insight
together.
Connect the PROFIBUS Adapter to PROFIBUS
Connect the PROFIBUS terminal to the PROFIBUS
DB9 connector located on the side of the module.
The connector has screws for positive retention to
eliminate accidental unplugging.
Connect 24 Vdc control power to the 5-position
header.
The connector has screws for positive reten-
tion to eliminate accidential unplugging.
Use one wire per terminal.
Set the PROFIBUS address
The PROFIBUS address is set using the DIP
switches located on the face of the module. The
PROFIBUS address is binary with the major units
numbered to the left of the switch on the side
label. Adding up the major units set to ON deter-
mines the address of the module.
Example: To set the address to 25, start from the
switch mark 32 and set the switches to Off (32),
ON (16), ON (8), OFF (4), OFF (2) ON (1) (16+8+1
=25).
Note: Address is only updated upon power up.
The PROFIBUS baud rate is set automatically
using an auto baud technology, there is no need
to set the baud rate. For more information on the
PROFIBUS attributes and how to modify them,
refer to the appropriate user manual. Motor Insight
MN04209001E, C440 MN04201001E or S611
MN03902011E.
adapter to Motor
PROFIBUS
or C440-COM-ADP the following pro-
®
Effective July 2010
Supersedes April 2010
The GSD file is located on the Eaton web site, go
to www.eaton.com.
C441S - 120 Vac Input Specification
Example: 120V ac IO Module
- All inputs are isolated.
- All common terminals are
connected together internally.
Specification
Number of Inputs
Nominal Voltage
Nominal Current
Operating Frequency
Signal Delay max.
Input type
C441Q - 24 Vdc Input Specification
Example: Non Isolating 24V dc input Source
- Input source power is taken from 5 pin
connector.
- Connect C and OV together.
- Use 24 to source Inputs.
Example: Isolated 24V dc Input Source
- The inputs must be supplied by an
external power source.
- Do not connect the external supply to
terminals 0V and 24.
- Connect isolated power source
between C and inputs.
-
+
24V dc
+
-
NET
Pin 1
I1
I1
I2
I2
I3
I3
I4
I4
C
C
C
C
120V ac
C
C
NO
Q1
NO
Q1
AC/DC
NO
Q2
C
C
NC
Q2
AC/DC
Pin 12
Value
4
120 Vac
15mA
50/60Hz
30ms
IEC 61131-2
Type 1 Digital
-
+
24V dc
+
-
NET
Pin 1
I1
I1
I2
I2
I3
I3
I4
I4
C
C
-
OV
-
24V dc
-
+
I/O Power
24
+
+
NO
Q1
NO
Q1
AC/DC
NO
Q2
C
C
NC
Q2
AC/DC
Pin 12
-
+
24V dc
+
-
NET
Pin 1
I1
I1
I2
I2
I3
I3
I4
I4
-
C
C
+
24V dc
OV
-
-
24V dc
-
+
I/O Power
24
+
+
NO
Q1
NO
Q1
AC/DC
NO
Q2
C
C
NC
Q2
AC/DC
Pin 12

Advertisement

loading

Summary of Contents for Eaton C440

  • Page 1 Supersedes April 2010 PROFIBUS Module for use with Motor Insight, C440 and S611 Installation The GSD file is located on the Eaton web site, go to www.eaton.com. The PROFIBUS module is designed to be used in industrial applications and installed in accordance C441S - 120 Vac Input Specification with this document.
  • Page 2 Installation Leaflet IL04209006E PROFIBUS Module for use with Motor Insight, C440 and S611 Effective July 2010 Setup the Device Parameters Specification Value Select the base module in the configuration to display its device Number of Inputs parameters. The base module contains the parameters to en- able/disable faults, set thresholds, etc.
  • Page 3 Current Draw Approx. 30 mA Notes For use with Eaton UL Listed Power Supply Catalog Nos. PSS55A, PSS55B, PSS55C, or PS160E. Any UL Listed isolated power supply with a maximum of 30 Vdc output may be used, provided that a UL Listed or Recognized Fuse rated no more than 3A maximum be installed.
  • Page 4 Installation Leaflet IL04209006E PROFIBUS Module for use with Motor Insight, C440 and S611 Effective July 2010 Eaton Corporation Electrical Sector 1000 Cherrington Parkway Moon Township, PA 15108 United States 877-ETN-CARE (877-386-2273) Eaton.com © 2009 Eaton Corporation PowerChain Management is a registered All Rights Reserved trademark of Eaton Corporation.