Group 21: Start/Stop - ABB ACS550 User Manual

Hide thumbs Also See for ACS550:
Table of Contents

Advertisement

128

Group 21: START/STOP

This group defines how the motor starts and stops. The ACS550 supports several
start and stop modes.
Code Description
2101 START FUNCTION
Selects the motor start method. The valid options depend on the value of parameter 9904
1 =
– Selects the automatic start mode.
AUTO
• Vector control modes: Optimal start in most cases. The drive automatically selects the correct output frequency to
start a rotating motor.
:
mode: Immediate start from zero frequency.
SCALAR
FREQ
2 =
– Selects the DC Magnetizing start mode.
DC MAGN
Note: The DC Magnetizing start mode cannot start a rotating motor.
Note: The drive starts when the set pre-magnetizing time (parameter 2103
magnetization is not complete.
• Vector control modes: Magnetizes the motor within the time determined by the parameter 2103
using DC current. The normal control is released exactly after the magnetizing time. This selection guarantees
the highest possible break-away torque.
:
mode: Magnetizes the motor within the time determined by the parameter 2103
SCALAR
FREQ
DC current. The normal control is released exactly after the magnetizing time.
3 =
– Selects the flying start mode.
SCALAR FLYST
• Vector control modes: Not applicable.
:
mode: The drive automatically selects the correct output frequency to start a rotating motor – useful
SCALAR
FREQ
if the motor is already rotating and if the drive will start smoothly at the current frequency.
4 =
– Selects the automatic torque boost mode (
TORQ BOOST
• May be necessary in drives with high starting torque.
• Torque boost is only applied at start, ending when output frequency exceeds 20 Hz or when output frequency is
equal to reference.
• In the beginning the motor magnetizes within the time determined by the parameter 2103
current.
• See parameter 2110
5 =
+
– Selects both the flying start and the torque boost mode (
FLY
BOOST
• Flying start routine is performed first and the motor is magnetized. If the speed is found to be zero, the torque
boost is done.
8 =
– Immediate start from zero frequency.
RAMP
2102 STOP FUNCTION
Selects the motor stop method.
1 =
– Selects cutting off the motor power as the stop method. The motor coasts to stop.
COAST
2 =
– Selects using a deceleration ramp.
RAMP
• Deceleration ramp is defined by 2203
2103 DC MAGN TIME
Defines the pre-magnetizing time for the DC Magnetizing start mode.
• Use parameter 2101 to select the start mode.
• After the start command, the drive pre-magnetizes the motor for the time defined here and then starts the motor.
• Set the pre-magnetizing time just long enough to allow full motor magnetization. Too long a time heats the motor
excessively.
2104 DC HOLD CTL
Selects whether DC current is used for braking or DC Hold.
0 =
– Disables the DC current operation.
NOT SEL
1 =
– Enables the DC Hold function. See the diagram.
DC HOLD
• Requires parameter 9904
• Stops generating sinusoidal current and injects DC into the motor when
both the reference and the motor speed drop below the value of parameter
2105.
• When the reference rises above the level of parameter 2105 the drive
resumes normal operation.
2 =
– Enables the DC Injection Braking after modulation has
DC BRAKING
stopped.
• If parameter 2102
• If parameter 2102
Parameters
.
TORQ BOOST CURR
DECELER TIME
MOTOR CTRL MODE
is 1 (
STOP FUNCTION
COAST
is 2 (
), braking is applied after ramp.
STOP FUNCTION
RAMP
:
mode only).
SCALAR
FREQ
SCALAR
1 or 2206
DECELER TIME
= 1 (
:
)
VECTOR
SPEED
), braking is applied after start is removed.
ACS550 User's Manual
MOTOR CTRL MODE
) has passed, even if motor
DC MAGN TIME
DC MAGN TIME
DC MAGN TIME
DC MAGN TIME
:
mode only).
FREQ
2 (whichever is active).
Motor
DC hold
speed
Ref
DC hold
speed
.
using
using DC
T
T