Setting
Priority
Example
Note
Setting
Special day
Holidays
62/226
Building Technologies
HVAC Products
(slaves). The time of the special day is a preselection made by the master and applies
to all controllers in the same holidays/special days zone.
5.2.4

Calendar entry

A maximum of 16 entries can be made. The entries are sorted in chronological order.
Every entry must include:
• Date, year and starting time
• Date and end time
• Reason for entry (holidays or special day)
Main menu > Holidays/special days > Calendar
Operating line
Entry 1... entry 16
Annually recurring holidays or special days can be entered by setting an asterisk (*) for
the annual setting.
If 2 entries overlap, following applies: Special days have priority over holidays. Hence, it
is also possible to have a special day during a holiday period.
An example of a special day during the holiday period would be a theatre performance
in a school building.
At the end of the holiday period or special day, operation according to the normal 7-day
program will be resumed. During this transition period, it can occur that optimum start
control (e.g. boost heating) cannot be started in due time. It is therefore recommended
to bring the end of the holiday period somewhat forward, thereby giving the plant suffi-
cient time to adapt to the respective setpoints.
5.2.5

Control inputs for holidays and special days

Holidays and special days can also be activated via digital inputs. For that purpose,
digital inputs must be assigned.
Main menu > Commissioning > Extra configuration > Miscellaneous > Inputs
Operating line
Holiday input
Special day input
* Here, the free inputs are available for selection
These inputs are only active if holidays/special day operation is set to "Autonomous" or
"Master".
The digital input enables the plant to constantly use the special day program set in the
7-day program without necessitating interventions on the controller.
When the configured input is activated, the special day program will become active.
This program is maintained until the input becomes inactive. Then, the normal 7-day
program will be resumed.
The digital input enables the plant to be constantly switched to "Holidays" mode without
necessitating interventions on the controller.
When the configured input is activated, the plant switches to the "Holidays" mode. This
program is maintained until the input becomes inactive. Then, the normal 7-day pro-
gram will be resumed.
Boiler Sequence Controller RMK770
5 General functions, fundamentals
Range
Start / End / Reason
Range
RMK770..., RMZ7...*
RMK770..., RMZ7...*
Factory setting
--- / --- / Holidays
Factory setting
---
---
CE1P3132en