Predefined Fault Inputs; Fault Inputs; Universal Fault Inputs - Siemens Synco700 RMK770 Documentation Handbook

Series modular boiler sequence controller
Table of Contents

Advertisement

182/226
Building Technologies
HVAC Products
again only after the fault has been acknowledged, the errors corrected and the fault
reset.
LED off
No fault,
acknowledged,
reset
Fault
coming
12.6

Predefined fault inputs

With function blocks "Boiler sequence manager", "Boiler 1...6" and the pump blocks,
predefined fault inputs are available.
For a description of these fault inputs, refer to the relevant function blocks. The parame-
ters of these fault inputs are also set on the respective function blocks.
12.7

Fault inputs

12.7.1 Universal fault inputs

The RMK770 provides 4 universal fault inputs. These can be activated in the extra
configuration.
Analog or digital inputs can be defined as fault inputs. Inputs D1 and D2 at the RMK770
can only be used as digital fault inputs.
If the input is not assigned to an input that has already been configured, the input identifier
and thus the type of input or the unit can be freely selected.
Main menu > Commissioning > Extra configuration > Faults > Input identifier
Operating line
Fault input 1
Fault input 2
Fault input 3
Fault input 4
With a digital input, it is also possible to define the normal position.
Main menu > Commissioning > Settings > Inputs > RMK770.D... (or RMZ78... )
Operating line
Normal position
Boiler Sequence Controller RMK770
12 Function block faults
Aggregate or plant stopped
LED lit
Acknowledge
fault
No fault,
acknowledged
Fault
going
Faulty,
acknowledged
Acknowledge
fault
LED lit
Range
°C / % / g/kg / kJ/kg /
W/m2 / m/s / bar / mbar /
Pa / ppm / Universal
0000.0 / Universal 000.0 /
Universal 0000 / Digital
Like fault input 1
Like fault input 1
Like fault input 1
Range
Open / Closed
LED flashes
No fault, not
acknowledged
Fault
coming
Fault
going
Faulty, not
acknowledged
LED flashes
Factory setting
Digital
Digital
Digital
Digital
Factory setting
Open
CE1P3132en